GE L30 Instruction Manual page 527

Line current differential system ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 9 of 63)
ADDR
REGISTER NAME
Source Power (Read Only) (2 modules)
1C00
Source 1 Three Phase Real Power
1C02
Source 1 Phase A Real Power
1C04
Source 1 Phase B Real Power
1C06
Source 1 Phase C Real Power
1C08
Source 1 Three Phase Reactive Power
1C0A
Source 1 Phase A Reactive Power
1C0C
Source 1 Phase B Reactive Power
1C0E
Source 1 Phase C Reactive Power
1C10
Source 1 Three Phase Apparent Power
1C12
Source 1 Phase A Apparent Power
1C14
Source 1 Phase B Apparent Power
1C16
Source 1 Phase C Apparent Power
1C18
Source 1 Three Phase Power Factor
1C19
Source 1 Phase A Power Factor
1C1A
Source 1 Phase B Power Factor
1C1B
Source 1 Phase C Power Factor
1C1C
Reserved (4 items)
1C20
...Repeated for Source 2
Source Frequency (Read Only) (2 modules)
1D80
Frequency for Source 1
1D82
Frequency for Source 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E0
Breaker 1 Arcing Current Phase A
21E2
Breaker 1 Arcing Current Phase B
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E4
Breaker 1 Arcing Current Phase C
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E6
Breaker 1 Operating Time Phase A
21E7
Breaker 1 Operating Time Phase B
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21E8
Breaker 1 Operating Time Phase C
21E9
Breaker 1 Operating Time
21EA
...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21EE
...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21F0
...Repeated for module number 2
Breaker Arcing Current Actual Values (Read Only Non-Volatile) (2 modules)
21F2
...Repeated for module number 2
Breaker Arcing Current Commands (Read/Write Command) (2 modules)
2224
Breaker 1 Arcing Current Clear Command
2225
Breaker 2 Arcing Current Clear Command
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
GE Multilin
RANGE
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-1000000000000 to
1000000000000
-0.999 to 1
-0.999 to 1
-0.999 to 1
-0.999 to 1
---
2 to 90
2 to 90
0 to 99999999
0 to 99999999
0 to 99999999
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 1
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
W
0.001
F060
W
0.001
F060
W
0.001
F060
W
0.001
F060
var
0.001
F060
var
0.001
F060
var
0.001
F060
var
0.001
F060
VA
0.001
F060
VA
0.001
F060
VA
0.001
F060
VA
0.001
F060
---
0.001
F013
---
0.001
F013
---
0.001
F013
---
0.001
F013
---
---
F001
Hz
0.001
F003
Hz
0.001
F003
2
kA
-cyc
1
F060
2
kA
-cyc
1
F060
2
kA
-cyc
1
F060
ms
1
F001
ms
1
F001
ms
1
F001
ms
1
F001
---
1
F126
---
1
F126
---
1
F126
DEFAULT
0
0
0
B
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (No)
0 (No)
0 (No)
B-17

Advertisement

Table of Contents
loading

Table of Contents