10.2001
Number / Fault
Cause
F091
The rotating measurement takes longer than
programmed in a measured status. Possible
Mld Time
causes:
Load torque too high
Load torque not uniform
Ramp-function generator disabled
F095
Due to entries for
- Permissible phase sequence
Mld n(set)
- Maximum frequency,
- Minimum speed,
- Changeover frequency between V and I
model,
- Start of field-weakening frequency,
- Frequency suppression bandwidth
it was not possible to determine a permissible
frequency range for the rotating measurement.
F096
The rotating measurement was aborted due to
the inadmissible external intervention.
Mld abort
F097
The measured values for the nominal ramp-up
time when optimizing the controller deviate too
Mld meausred value
greatly.
Cause: very unsteady load torque
F098
The rotating measurement has detected a fault
in the speed actual value signal. The fault
Mld Tachof
value defines the type of fault.
The fault measurement may have been
erroneously generated if the drive speed is
externally forced (e.g. completely locked drive
generates the "no signal" message)
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
www.aotewell.com
Operating Instructions
sales@aotewell.com
Counter-measure
Eliminate the cause and re-start the
measurement (power up the converter again).
If it re-occurs, replace CU, or replace the unit
(Compact PLUS).
There must be a 10% frequency range which
lies above 1.1 times the changeover frequency
and below 0.9 times the start of field-
weakening frequency.
Possible counter-measures
- Permit both phase sequences
- Increase maximum frequency
- Reduce minimum speed,
- Reduce changeover frequency between the
V and I model.
- Reduce or remove the frequency
suppression bandwidth.
The fault value in r949 defines the type of
intervention:
4 Setpoint inhibit
5 Changeover, setpoint channel
8 Unexpected change in the converter status
12 Motor data set changeover (for function
selection "Compl. Mot ID")
13 Changeover to slave drive
14 Motor data set changeover to data set with
v/f_charac
15 Controller inhibit is set
16 Ramp-function generator is disabled
17 Selection "Tacho test" for F controller
18 Ramp-function generator stopped
Eliminate cause
22 Inverter inhibit:
Check inverter release (P561)
If necessary, increase the torque limit values
to 100 percent
The fault value in r949 defines the type of
intervention
4 No speed signal present
5 Sign of the signal is incorrect
6 A track signal is missing
7 Incorrect gain
8 Incorrect pulse number
Checking the measurement cables.
Checking the parameters
- P130 Src Speed ActV
- P1151 Encoder Pulse #
Industry Automation
Faults and Alarms
13-11