Parameterization
8.3
Parameter input with DriveMonitor
8.3.1
Installation and connection
8.3.1.1
Installation
8.3.1.2
Connection
RS232 interface
RS485 interface
8-6
www.aotewell.com
Operation of DriveMonitor via the PC and USS interfaces is described
below.
A CD is included with the devices of the MASTERDRIVES Series when
they are delivered. The operating tool supplied on the CD
(DriveMonitor) is automatically installed from this CD. If "automatic
notification on change" is activated for the CD drive on the PC, user
guidance starts when you insert the CD and takes you through
installation of DriveMonitor. If this is not the case, start file
"Autoplay.exe" in the root directory of the CD.
There are two ways of connecting a PC to a device of the SIMOVERT
MASTERDRIVES Series via the USS interface. The devices of the
SIMOVERT MASTERDRIVES Series have both an RS232 and an
RS485 interface.
The serial interface that PCs are equipped with by default functions as
an RS232 interface. This interface is not suitable for bus operation and
is therefore only intended for operation of a SIMOVERT
MASTERDRIVES device.
1
6
2
7
3
8
4
9
5
To PC COMx
socket
Fig. 8-2
Connecting cable for connecting PC COM(1-4) to SIMOVERT
MASTERDRIVES X300
The RS485 interface is multi-point capable and therefore suitable for
bus operation. You can use it to connect 31 SIMOVERT
MASTERDRIVES with a PC. On the PC, either an integrated RS485
interface or an RS232 ↔ RS485 interface converter is necessary. On
the device, an RS485 interface is integrated into the -X103 connection.
For the cable: see pin assignment -X300 and device documentation of
the interface converter.
sales@aotewell.com
6
7
8
9
Device side
-X300 (compact PLUS -X103)
9-pin SUB-D connector
6SE7087-6JP60
Operating Instructions
SIMOVERT MASTERDRIVES
Industry Automation
05.2003
X300:
1
1 Ground
2
2 RxD (RS232)
3 Rx+/Tx+ (RS485)
3
4
5 Ground
4
6 +5V (OP1S)
7 TxD (RS232)
5
8 Rx-/Tx- (RS485)
9 Ground
Siemens AG
+86-755-8660-6182