Number / Alarm
Cause
A044
Only for synchronous motors (P095=12) in
operation:
I too low
The difference smoothed with P159 between
excitation current setpoint and actual value
(r160 - r156) deviates from zero by more than
25% of the rated magnetizing current.
A045
The DC braking function has been activated
and the motor frequency is still above the
DC braking activated
frequency at which DC braking begins (P398).
A049
At serial I/O (SCB1 with SCI1/2), no slave is
connected or fiber-optic cable is interrupted or
No slave
slaves are without voltage.
not Compact PLUS
A050
At ser. I/O the slaves required according to a
parameterized configuration are not present
Slave incorrect
(slave number or slave type): Analog inputs or
outputs or digital inputs or outputs have been
not Compact PLUS
parameterized which are not physically
present.
A051
In a peer-to-peer connection a baud rate has
been selected which is too high or too
Peer baud rate
different.
not Compact PLUS
A052
In a peer-to-peer connection, a PcD length has
been set which is too high (>5).
Peer PcD L
not Compact PLUS
A053
In a peer-to-peer connection, the pcD length of
transmitter and receiver do not match.
Peer Lng f.
not Compact PLUS
A057
Occurs when a TB is logged on and present,
but parameter tasks from the PMU, SCom1 or
TB Param
SCom2 have not been answered by the TB
within 6 seconds.
not Compact PLUS
A061
An active signal is present at binector U065
(1).
Alarm 1
Function blocks
A062
An active signal is present at binector U066
(1).
Alarm 2
Function blocks
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
www.aotewell.com
Operating Instructions
sales@aotewell.com
Counter-measure
Only for synchronous motors P095=12)
Check:
- whether the current limitation of the excitation
current control is too small,
- whether the dynamic performance of the
excitation current injection is too low,
- whether the excitation current injection
function is operating,
- whether the wiring of excitation current
actual-value P155 is correct,
- whether the wiring of excitation current
setpoint r160 is correct,
- whether there is a wire break between
MASTERDRIVES and the excitation device,
- whether the voltage limitation is too low for
dynamic excitation current control,
- whether the analog output for r160 takes
place without isolating amplifiers (despite
cable length > 4 m)
- Increase frequency at which DC braking
begins
P690 SSCI AnaIn Conf
- Check slave.
- Check cable.
Check parameter P693 (analog outputs), P698
(digital outputs). Check connectors
K4101...K4103, K4201...K4203 (analog inputs)
and binectors B4100...B4115, B4120...B4135,
B4200...B4215, B4220...B4235 (digital inputs)
for connecting.
Adjust the baud rate in conjunction with the
SCB boards P701 SCom/SCB Baud Rate
Reduce number of words P703 SCom/SCB
PcD #
Adjust the word length for transmitter and
receiver
P703 SCom/SCB PcD #
Replace TB configuration (software)
Check cause of alarm (see FD 710)
Check cause of alarm (see FD 710)
Industry Automation
Faults and Alarms
13-21