Control Terminal Strip X102 - Siemens 6SE7011-5EP60 Operating Instructions Manual

Simovert masterdrives vector control series frequency converter (ac-ac) compact plus type
Table of Contents

Advertisement

Connecting-up
X102 -
Control terminal
strip
7-16
www.aotewell.com
♦ 10 V auxiliary voltage (max. 5 mA) for supplying external
potentiometers
♦ Analog output, suitable for use as current or voltage output
♦ 1 analog input, suitable for use as current or voltage input
♦ 1 additional digital input
♦ 1 floating NO contact
Terminal
Designation
13
P10 V
14
N10 V
15
AO2
16
M AO2
17
AI2
18
M AI2
19
DI7
20
HS1
21
HS2
Connectable cross-section: 0.14 mm
Table 7-17

Control terminal strip X102

sales@aotewell.com
Meaning
+ 10 V supply for ext.
potentiometers
− − − − 10 V supply for ext.
potentiometers
Analog output 2
Ground for analog output 2
Analog input 2
Ground for analog input 2
Digital input 7
NO contact
(floating)
2
to 1.5 mm
6SE7087-6JP60
Operating Instructions
SIMOVERT MASTERDRIVES
Industry Automation
05.2003
Range
+ 10 V ± 1.3 %
I max = 5 mA
− − − − 10 V ± 1.3 %
I max = 5 mA
10 bit + sign
Voltage:
± 10 V / I max = 5 mA
Current:
0...20 mA R ≤ 500 Ω
11 bit + sign
Voltage:
± 10 V / Ri = 60 kΩ
Current:
Rin = 250 Ω
24 V, 10 mA
DC 30 V / max. 0.5 A
Minimum load 7 mA
2
(AWG 16)
Siemens AG
+86-755-8660-6182