Siemens 6SE7011-5EP60 Operating Instructions Manual page 119

Simovert masterdrives vector control series frequency converter (ac-ac) compact plus type
Table of Contents

Advertisement

Faults and Alarms
Number / Fault
Cause
F040
Incorrect operating status
AS internal
F041
A fault has occurred when storing the values in
the EEPROM.
EEPROM fault
F042
Calculating time problems
Calculating time
F044
A fault has occurred during the softwiring of
binectors and connectors.
BICO manager fault
F045
A hardware fault has occurred when accessing
an optional board
Opt. Board HW
F046
A fault has occurred during the transfer of
parameters to the gating unit processor.
Par. Task
F047
The calculating time in the gating unit
computer is not sufficient
Gating Calc Time
F048
The pulse frequency set in P340 is not
permissible.
Gating Pulse Freq
F049
The firmware versions on the CU have
different firmware release.
SW version
F050
Error when initializing the TSY board
TSY Init.
not Compact PLUS
F051
Digital tachometer or analog tachometer
sensing are faulty
Speed encoder
13-6
www.aotewell.com
Operating Instructions
sales@aotewell.com
Counter-measure
Replace CU (-A10), or replace the unit
(Compact PLUS)
Replace CU (-A10), or replace the unit
(Compact PLUS)
Reduce the calculating time load:
- Increase P357 Sampling Time
- Calculate individual blocks in a slower
sampling time
Observe r829 CalcTimeHdroom.
Störwert r949:
>1000 : Fault during softwiring of connectors
>2000 : Fault during softwiring of binectors
- Voltage OFF and ON
- Factory setting and new parameterization
- Replace the board
- Replace CU, or replace the unit (Compact
PLUS)
- Check connection of the board subrack to the
optional boards and replace if necessary.
Power the unit down and up again.
Replace CU (-A10), or replace the unit
(Compact PLUS)
Replace CU (-A10), or replace the unit
(Compact PLUS)
In case of synchronous motors (P095 = 12):
Pulse frequency set too high (P340 > 2 kHz).
Change P340 Pulse Frequency.
Use uniform firmware
Check:
- Whether the TSY is correctly inserted
Check the parameters:
- P130 Src SpdActV
- P151 Pulse #
- P138 AnalogTachScale
- P109 Motor #PolePairs
The product of P109 and P138 must be
smaller than 19200. Check or replace
tachometer. Check connection to tachometer.
- Replace CU, or replace the unit (Compact
PLUS)
6SE7087-6JP60
SIMOVERT MASTERDRIVES
Industry Automation
10.2001