Number / Fault
Cause
F145
See TB documentation
Technology board fault
not Compact PLUS
F146
See TB documentation
Technology board fault
not Compact PLUS
F147
See TB documentation
Technology board fault
not Compact PLUS
F148
An active signal is present at binector U061
(1).
Fault 1
Function blocks
F149
An active signal is present at binector U062
(1).
Fault 2
Function blocks
F150
An active signal is present at binector U063
(1).
Fault 3
Function blocks
F151
An active signal is present at binector U064
(1).
Fault 4
Function blocks
F152
After an appropriate number of invalid signs of
life, the sign of life monitoring block has gone
Signs of life repeatedly
into fault status.
invalid.
F243
Fault in internal linking. One of the two linked
partners does not reply.
Link int.
F244
Fault in the internal parameter linking
ParaLink int.
F255
A fault has occurred in the EEPROM.
Fault in EEPROM
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
www.aotewell.com
Table 13-1
Fault numbers, causes and their counter-measures
Operating Instructions
sales@aotewell.com
Counter-measure
Examine cause of fault, see function diagram
710
Examine cause of fault, see function diagram
710
Examine cause of fault, see function diagram
710
Examine cause of fault, see function diagram
710
Check cause of fault, see function diagram
170
Replace CU (-A10), or replace the unit
(Compact PLUS)
Release comparison of gating unit software
and operating software regarding the transfer
parameters.
Replace CU (-A10), or replace the unit
(Compact PLUS)
Switch off the unit and switch it on again. If the
fault re-occurs, replace CU, or replace the unit
(Compact PLUS)