Installing
3.3 Installing Control Unit
The factory settings described above for USS and PROFIBUS/PROFINET terminals
correspond to default setting 12 (two-wire control using method 1) or default setting 7
(switchover between fieldbus and jog using DI 3).
See also: Default settings of the terminal strip (Page 28).
3.3.3
Default settings of the terminal strip
Default setting 1: Two fixed speeds
Control Units CU240E-2
Selected with
STARTER: Conveyor technology
•
with 2 fixed frequencies
BOP-2: coN 2 SP
•
Fieldbus interface is not active.
DI 4 and DI 5 = high: The inverter adds
both fixed speeds.
Default setting 4: PROFIBUS or
PROFINET
Control Units CU240E-2
Selected with
STARTER: Conveyor systems with
•
fieldbus
BOP2: coN Fb
•
PROFIdrive telegram 352
28
Default setting 2: Two fixed speeds
with safety function
Control Units CU240E-2
Selected with
STARTER: Conveyor systems with
•
Basic Safety
BOP-2: coN SAFE
•
Fieldbus interface is not active.
Default setting 5: PROFIBUS or
PROFINET with safety function
Control Units CU240E-2
Selected with
STARTER: Conveyor systems with
•
fieldbus and Basic Safety
BOP-2: coN Fb S
•
PROFIdrive telegram 352
Default setting 3: Four fixed speeds
Control Units CU240E-2
Selected with
STARTER: Conveyor technology
•
with 4 fixed frequencies
BOP-2: coN 4 SP
•
Fieldbus interface is not active.
Multiple DIs = high: The inverter adds
the corresponding fixed speeds.
Default setting 6: PROFIBUS or
PROFINET with two safety functions
CU240E-2 F, CU240E-2 DP-F, and
CU240E-2 PN-F Control Units
Selected with
STARTER: Fieldbus with Extended
•
Safety
BOP-2: Fb SAFE
•
PROFIdrive telegram 1
Converter with Control Units CU230P-2; CU240B-2; CU240E-2