Figure 15. Flowmeter Field Wiring for F
B
A
(The power supply, filter,
first terminator, and
configuration tool are
typically located in the
control room.)
A. Power Supply
B. Integrated Power Conditioner and Filter
C. Terminators
D. Fieldbus Segment
E. (Trunk)
F. (Spur)
G. Devices 1 through 16
Cover jam screw
For transmitter housings shipped with a cover jam screw, the screw should be
properly installed once the transmitter has been wired and powered up. The
cover jam screw is intended to disallow the removal of the transmitter cover in
flameproof environments without the use of tooling. Follow these steps to install
the cover jam screw:
1. Verify the cover jam screw is completely threaded into the housing.
2. Install the transmitter housing cover and verify the cover is tight against the
housing.
3. Using an M4 hex wrench, loosen the jam screw until it contacts the
transmitter cover.
4. Turn the jam screw an additional
cover.
Note
Application of excessive torque may strip the threads.
1. Intrinsically safe installations may allow fewer devices per I.S. barrier.
6234 ft (1900 m) max
(depending upon cable
characteristics)
C
D
E
(1)
Fieldbus Protocol
OUNDATION
G
/
turn counterclockwise to secure the
1
2
Quick Start Guide
15