PRODUCT SETUP
The D30 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B
signals. UTC time is provided by SNTP servers.
The real-time clock (RTC) and time stamps reported in historical records and communication protocols can be incorrect if
the Local Time settings are not configured properly.
See the IRIG-B section in the Installation chapter for guidance on these settings when using an IRIG-B source that sets the
IRIG-B control bits according to IEEE Std 1344-1995.
LOCAL TIME OFFSET FROM UTC
zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative values. A value
of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is synchronized with a
communications protocol providing only local time or it is free-running, the offset setting is used to calculate UTC from the
local time these provide. When the RTC is synchronized with a communications protocol providing only UTC (such as PTP or
SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time.
DAYLIGHT SAVINGS TIME
when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and
so the DST settings are ignored.

5.3.8 Fault reports

SETTINGS  PRODUCT SETUP  FAULT REPORTS  FAULT REPORT 1
 FAULT REPORT 1
5
5-112
— Used to specify the local time zone offset from UTC (Greenwich Mean Time) in hours. Time
and
— Can be used to allow the relay to follow the DST rules of the local time zone. Note that
DST
FAULT REPORT 1
SOURCE: SRC 1
FAULT REPORT 1 TRIG:
Off
FAULT REPORT 1 Z1
MAG: 3.00 Ω
FAULT REPORT 1 Z1
ANGLE: 75°
FAULT REPORT 1 Z0
MAG: 9.00 Ω
FAULT REPORT 1 Z0
ANGLE: 75°
FAULT REPORT 1 Z0M
MAG: 0.00 Ω
FAULT REPORT 1 Z0M
ANGLE: 0°
FAULT REPORT 1 LINE
LENGTH UNITS: km
FAULT REP 1 LENGTH
(km ): 100.0
FAULT REPORT 1 VT
SUBSTITUTION: None
FAULT REP 1 SYSTEM
Z0 MAG: 2.00 Ω
FAULT REP 1 SYSTEM
Z0 ANGLE: 75°
FAULT REPORT 1 Z0M
MAG: 0.00 Ω
Range:
SRC 1, SRC 2
Range:
FlexLogic operand
Range:
0.01 to 250.00 ohms in steps of 0.01
Range:
25 to 90° in steps of 1
Range:
0.01 to 650.00 ohms in steps of 0.01
Range:
25 to 90° in steps of 1
Range:
0.00 to 650.00 ohms in steps of 0.01
Range:
25 to 90° in steps of 1
Range:
km, miles
Range:
0.0 to 2000.0 in steps of 0.1
Range:
None, I0, V0
Range:
0.01 to 650.00 ohms in steps of 0.01
Range:
25 to 90° in steps of 1
Range:
0.00 to 650.00 ohms in steps of 0.01
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS