Current Sensor Offset Fault; Car Moving On Wrong Direction; Door Bridging Failure; Limited Feature - Arkel ARCODE Quick Installation Manual

Integrated elevator controller for traction lifts
Table of Contents

Advertisement

Available languages

Available languages

Arkel Elektrik Elektronik San. ve Tic. A.Ş.

58-Current sensor offset fault:

values for 1 second, it gives this error.
- Check the current sensor values at the "info" and "system information" screen
- Get contact to Arkel support

59-Car moving on wrong direction:

active, or if the reference speed of car is negative and 818 signal turns to passive from active, it gives this error.
- If the error is received during movement in the up direction, check 817 signal. If error is received during movement
in the down direction, check 818 signal.
- Check that there is no short circuit or cutting on 817,818 signals.
- Check that there is no crack on 817,818 conenction cables.
- Check the motor direction is correct by driving motor in inspection mode.

60-Door bridging failure:

- There may be a problem about DBR board.
- ML1 and ML2 signals may get electrical noise.
61-UDI exception:
CPU error. Get contact to Arkel support
62-Overflow exception:
63-Watchdog timeout
: CPU error. Get contact to Arkel support
71-Licence key (dongle) not found:
Highline, and there is no dongle, it gives this error. If it is Midline, the dongle which is proper to Midline should be used.
If it is Highline, the dongle which is proper to Highline should be used.

72- Limited feature:

- If "P0839 ARCODE class" is chosen ARCODE Basic and if one of the following cases
exists, it gives this error.
-"P0002: number of floors", if it is entered greater than 16.
-"P0135: maximum travel speed", if it is entered greater than 1,6 m/s.
-if the number of Arcode is more than 2 in the system.
-"P0890: Priority service function", if it is chosen as "Enabled".
-"P0942: Park floor selection method", if it is chosen as "park floor is selected by time zone".
- If "P0839 ARCODE class" is chosen as ARCODE Midline and if one of the following cases exists, it gives this error.
-"P0002: number of floors", if it is entered greater than 24.
-"P0135: maximum travel speed", if it is entered greater than 2,5 m/s.
73- Detected entry inside shaft:
protection switch Floor-*" signals are active and the car is not on that floor, this error will be triggered. (Normally there
shouldn't be any signal if the door is closed)
- Check the door contacts and signal positions of SPR programmable inputs.
Note: This is a permanent error. In order to get rid of the permanent error case, look at Appendix-3.
80-Current was near motor limit continuously:
multiplication of "P0159 nominal motor current" and "P0429 motor overcurrent limit" for 6 seconds, it gives this error.
- Check motor parameters
ARKEL
If U,V,W current sensor offset values are not interval of max. and min. accepted
If the reference speed of car is positive and 817 signal turns to passive from
If a problem is detected about DBR board, this error is received.
CPU error. Get contact to Arkel support
This is related to "P0839" Arcode class. If "P0839" is chosen as Midline or
When the shaft entry protection is active, if any of "(SPR*) Shaft entry
68
If motor current exceeds over the value which is the
www.arkel.com.tr
ARCODE