SP-16 SETTINGS

SP-16 card is used when buttons are not serial communication (CANBus). It can serve up to 16 floors at most. In one way
collective external calls can be collected up to 16 floors with a SP-16. In case of two way collective, calls can be collected
up to 9 floors with a SP-16. For double buttons 16 floors two SP-16 must be used. Dip switch settings must be done
according to the following table.
CALL TYPE / DOOR /
DIRECTION CHOICE
One-Way Collective (2-16 Stop)/
Door A /
Down
One-Way Collective (2-16 Stop)/
Door B /
Down
Two-Way Collective (2-9 Stop) /
Door A /
Up & Down
Two-Way Collective (2-9 Stop) /
Door B /
Up & Down
Two-Way Collective (10-16Stop)
Door A /
Up
Two-Way Collective (10-16Stop)
Door B /
Up
Two-Way Collective (10-16Stop)
Door A /
Down
Two-Way Collective (10-16Stop)
Door B /
Down
ARKEL
DS2
DS1
DS3
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
Figure-3: SP-16 dipswitch settings
59
I1 I2 I3.........I7 I8 I9 I10............I14 I15 I16
301 202 203.................................214 215 216
301 202 203.................................214 215 216
301 302 303.....307 308 202 203.......207 208 209
301 302 303.....307 308 202 203.......207 208 209
301 302 303.................................314 315 -
301 302 303.................................314 315 -
- 202 203.................................214 215 216
- 202 203.................................214 215 216
www.arkel.com.tr
Appendix-1