Replacing The 2145 Ups-1U; The 2145 Ups-1U Internal Battery Connector; Mounting Screws For The 2145 Ups-1U - IBM SAN Volume Controller 2145-CG8 Hardware Maintenance Manual

System storage san volume controller series
Hide thumbs Also See for SAN Volume Controller 2145-CG8:
Table of Contents

Advertisement

Figure 312. The 2145 UPS-1U internal battery connector with protective tape
8. Reinstall the front panel.
9. At the front of the 2145 UPS-1U, unscrew the two mounting screws
1
Figure 313. Mounting screws for the 2145 UPS-1U
10. From the back of the rack, push the 2145 UPS-1U forward approximately 5 cm (2 in) to enable you
to pull it from the rack.
11. Go to the front of the rack.
12. Pull the 2145 UPS-1U forward and remove it from the rack.

Replacing the 2145 UPS-1U

You can replace the 2145 UPS-1U only after you remove the previous uninterruptible power supply.
|
Use the reference numbers in parentheses at the end of each notice, such as (C003) for example, to find
the matching translated notice in IBM System Storage SAN Volume Controller Safety Notices.
|
1
, as shown in Figure 313.
Chapter 2. Removing and replacing parts
309