Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
76
IEC140000134 V1 EN-US
1.1. Navigate to the Settings tab.
1.2. Force the IP stack to IPv4 by setting the parameter ForceIPv4 to True.
2.
Set the Connection Parameters on PMU Connection Tester for TCP
communication according to the PMU configuration.
IEC140000135 V1 EN-US
2.1. Set Host IP to the PMU IP address configured for the port in use. Here
the LANAB:1 IPAddress (192.168.1.10) is set.
2.2. Set Port to the IED's TCP port set in the PMU under parameter
C37.118TCPport (4712 is default). Alternatively, in order to make an
1MRK 504 165-UEN A
IEC140000134-1-en.vsd
IEC140000135-1-en.vsd
Transformer protection RET670 2.2 IEC
Commissioning manual