Section 15
Troubleshooting
298
Headline
Invalid value set for PMU Parameters
Invalid phase angle reference
GOOSE is configured on a disabled port
LDCM not running the application image
LDCM version is not accepted
OEM not running the application image
SFP unplugged from the slot
SFP replaced with other type
Non ABB vendor SFP detected
1MRK 504 165-UEN A
Explanation
There are two explanations possible:
Check if the following parameters are set
ReportRate or
correctly on PMUREPORT:
SvcClass or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set
ReportRate or
correctly on PMUREPORT:
SvcClass or RptTimetag or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
PhaseAngleRef corresponds to an
The selected
analog channel that is not configured. Please
configure a valid reference channel.
At least one of the access points configured for
GOOSE is disabled. The port can be disabled
either through changing the access point
operation to off or by unchecking the GOOSE
protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Please enable GOOSE on access points:
AP_FRONT, AP_1
<slot number> is running the factory image
instead of the application image. The factory
image is older and does not contain the latest
updates and fixes.
Please reboot the IED. If the problem persists
update the LDCM firmware or replace the board.
<device name> firmware version <version
string> is not accepted. The minimum accepted
version is <version string>.
Please update the LDCM firmware or replace the
board.
OEM in slot <slot number> is running the factory
image instead of the application image. The
factory image is older and does not contain the
latest updates and fixes.
Please reboot the IED. If the problem persists,
update the OEM firmware or replace the board.
SFP has been unplugged from the slot
Please check the connection.
Corresponding hardware(s) is set to fail.
Configured and the detected SFP(s) are
different. Corresponding hardware(s) is set to
fail.
Please restart IED and consider Reconfigure HW
modules to get updated hardware list.
Non ABB vendor SFP detected.
Corresponding hardware(s) is set to fail. Please
use ABB approved SFP's.
Transformer protection RET670 2.2 IEC
Commissioning manual