ABB RET670 Commissioning Manual page 129

Relion 670 series, transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 165-UEN A
Transformer protection RET670 2.2 IEC
Commissioning manual
Testing functionality by secondary injection
Table 26:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPP x tan (ArgRLd)
R
0.85 x RFPP
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
RLdFw x tan (ArgLd)
R
0
8
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
9
X
–0.4 x RLdFw x tan(ArgDir)
R
0.4 x RLdFw
10
X
0.5 x X1
R
–0.23 x X1
11
X
0.8 x X1
R
–0.37 x X1
12
X
0.5 x X1
R
0.5 x R1
13
X
0
R
0.5 x RFPP
Table 27:
Test points for phase-to-earth L3-E (Ohm/Loop)
Test point
Reach
Value
1
X
R
2
X
R
3
X
R
Table continues on next page
set
set
set
set
+ RFPP/2
set
set
+ RFPP/2
set
set
set
set
set
set
set
(2 x X1
+X0
)/3
set
set
0
(2 x X1
+ X0
)/3
set
set
2 x R1
+ R0
)/3
set
set
0.8 x (2 x X1
+ X0
)/3
set
set
0.8 x (2 x R1
+ R0
)/3
set
set
+RFPE
set
Section 11
Comments
ArgRLd = angle for the maximal
load transfer
Exact: 0.8 x RFPP/2 (ArgDir)
Exact –0.5 x R1
x
set
tan(ArgNegRes-90)
Exact –0.5 x R1
x
set
tan(ArgNegRes-90)
OperationLdCmp
Only used when
setting is 0 (Off)
Comments
123

Advertisement

Table of Contents