ABB RET670 Commissioning Manual page 165

Relion 670 series, transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 165-UEN A
Transformer protection RET670 2.2 IEC
Commissioning manual
Testing functionality by secondary injection
ForwardX
V
arctan
=
ts
ForwardR
EQUATION14058 V1 EN-US
frequency of V
= 50 Hz
ts
I
= 0 A
50s
I
= 0 A
tfs
State 2: main test step.
Define the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V
VT s
,
V
0 9
.
V
=
×
×
ts
t RZ
,
1
V
VT p
,
EQUATION14066 V1 EN-US
ForwardX
V
arctan
=
ts
ForwardR
EQUATION14058 V1 EN-US
frequency of V
= 50 Hz
ts
I
CTs
I
I
10459
=
×
=
50
s
50
I
CTp
EQUATION14059 V1 EN-US
∠I
= 0º
50s
frequency of I
= 50 Hz
50s
I
CTs
It
I
10459
=
×
=
tf
fs
I
CTp
EQUATION14062 V1 EN-US
∠I
= 180º
tfs
frequency of I
= 49.5 Hz
tfs
Expected result: start of the protection function and trip in zone 1 when trip
conditions are fulfilled.
59 33
.
arctan
82. . 14°
 =
 =
8 19
.
0 1
.
0 9 1435
.
9 36
.
V
=
×
×
=
13 8
.
59 33
.
arctan
82. . 14°
 =
 =
8 19
.
1
= .
1 162
A
×
9000
1
1 162
.
A
×
=
9000
Section 11
(Equation 52)
(Equation 53)
(Equation 54)
(Equation 55)
(Equation 56)
159