Section 11
Testing functionality by secondary injection
116
4
X +
(
1
XN
)
50% of RLdFw
IEC09000734 V4 EN-US
Figure 25:
Operating characteristic for phase selection function, forward
direction single-phase faults
Table 22:
Test points for phase-to-earth loop L3-E (Ohm/loop)
Test point
Reach
Value
1
X
[X1+XN]
R
0
2
X
0
R
RLdFw
R
RFFwPE
3
X
0.85·[X1+XN]
R
0.85·[X1+XN]·1/tan(60°)+RFFwPE
4
X
0.85·[X1+XN]
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
5
X
RFFwPE·tan (ArgLd)
R
RFFwPE
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
Table
22
is used together with figure 25.
W
(
/
loop
)
X
1
85%
5
ArgNegRes
2
7
6
RFFwPE
1MRK 504 165-UEN A
3
60°
W
(
/
loop
R
IEC09000734-4-en.vsd
Comments
XN=(X
-X
)/3
0
1
When RLdFW < RFFwPE
When RLdFwPE > RFFwPE
R≈0.491·(X1+XN)+RFFwPE
Can be limited by RFFwPE
Only when RLdFw < RFFwPE
Transformer protection RET670 2.2 IEC
Commissioning manual
)