ABB RET670 Commissioning Manual page 168

Relion 670 series, transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
162
Expected result: start of the protection function and trip in zone 1 when trip
conditions are fulfilled.
The trajectory of the impedance does not enter the lens characteristic
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs to check the available
service values of the function block OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V
VT s
,
V
1 1
.
V
=
×
×
ts
t RvsZ
,
V
VT p
,
EQUATION14069 V1 EN-US
æ
ReverseX
Ð
=
ç
V
arctan
è
ts
ReverseR
EQUATION14068 V1 EN-US
frequency of V
= 50 Hz
ts
I
CTs
I
I
10459
=
×
=
50
s
50
I
CTp
EQUATION14059 V1 EN-US
∠I
= 0º
50s
frequency of I
= 50 Hz
50s
I
CTs
It
I
10459
=
×
=
tf
fs
I
CTp
EQUATION14062 V1 EN-US
∠I
= 0º
tfs
frequency of I
= 50 Hz
tf
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are
according to the injected quantities and that ROTORANG is close to 0 rad. For
this particular injection the service values are:
VOLTAGE= 6.49 kV
CURRENT= 20918 A
R= –0.32%
X=–32.57%
ROTORANG= 0.08 rad
Note that these values identify a point outside the lens characteristic, even if it
is close to the point SE. Neither START nor TRIP is issued.
0 1
.
1 1 5899
.
47 02
.
=
×
×
=
13 8
.
ö
æ
29.60
÷
-
° =
ç
180
arctan
ø
è
0.29
1
= .
1 162
A
×
9000
1
1 162
.
A
×
=
9000
1MRK 504 165-UEN A
GUID-189FECED-12A7-4A41-BCCF-D93C0FF9FA41 v1
GUID-448D5357-6CC2-438E-83CA-25FD381B7DFF v1
V
ö
÷
-
° = -
°
180
90.56
ø
Transformer protection RET670 2.2 IEC
Commissioning manual
(Equation 67)
(Equation 68)
(Equation 69)
(Equation 70)