Test Of The Point Se (R Rvsr , X Rvsx ) - ABB RET670 Commissioning Manual

Relion 670 series, transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
11.4.12.4
160
Test of the point SE (R
The trajectory of the impedance traverses the lens characteristic in
zone 1
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs to check the available
service values of the function block OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V
VT s
,
V
0 9
.
V
=
×
×
ts
t RvsZ
,
V
VT p
,
EQUATION14067 V1 EN-US
æ
ReverseX
Ð
=
ç
V
arctan
è
ts
ReverseR
EQUATION14068 V1 EN-US
frequency of V
= 50 Hz
ts
I
CTs
I
I
10459
=
×
=
50
s
50
I
CTp
EQUATION14059 V1 EN-US
∠I
= 0º
50s
frequency of I
= 50 Hz
50s
I
CTs
It
I
10459
=
×
=
tf
fs
I
CTp
EQUATION14062 V1 EN-US
∠I
= 0º
tfs
frequency of I
= 50 Hz
tf
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are
according to the injected quantities and that ROTORANG is close to 3.14 rad.
For this particular injection the service values are:
VOLTAGE = 5.31 kV
CURRENT = 20918 A
R = -0.26%
X = -26.65%
ROTORANG = -3.06 rad
Note that these values identify a point inside the lens characteristic in zone 1
that is close to the point SE. The START is issued, but no TRIP is performed.
, X
)
RvsR
RvsX
0 1
.
0 9 5899
.
38 47
.
=
×
×
=
13 8
.
ö
æ
29.60
-
° =
÷
ç
180
arctan
ø
è
0.29
1
= .
1 162
A
×
9000
1
1 162
.
A
×
=
9000
1MRK 504 165-UEN A
GUID-335F54E6-52DE-4BF1-A34B-0C2DB8059CC1 v1
GUID-2DD20D2E-6188-4631-A584-5E68B212E011 v1
GUID-7BCF3D7B-1B84-46D4-B9E3-066894A878E8 v1
V
ö
-
° = -
°
÷
180
90.56
ø
Transformer protection RET670 2.2 IEC
Commissioning manual
(Equation 57)
(Equation 58)
(Equation 59)