ABB RET670 Commissioning Manual page 155

Relion 670 series, transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 165-UEN A
Transformer protection RET670 2.2 IEC
Commissioning manual
Testing functionality by secondary injection
Considering the resistances and reactances which are related to the settings
(ForwardR, ForwardX) and (ReverseR, ReverseX):
ForwardR
R
ZBase
=
×
FwdR
100
EQUATION14048 V1 EN-US
ForwardX
X
ZBase
=
×
FwdX
100
EQUATION14049 V1 EN-US
ReverseR
R
ZBase
=
×
RvsR
100
EQUATION14050 V1 EN-US
ReverseR
X
ZBase
=
×
RvsX
100
EQUATION14051 V1 EN-US
and the voltages that are related to them:
2
V
Z
I
R
=
×
=
t FwdZ
,
FwdZ
t
FwdR
EQUATION14052 V1 EN-US
2
V
Z
I
R
=
×
=
t RvsZ
,
RvsZ
t
RvsR
EQUATION14053 V1 EN-US
The previous calculations are in primary values. They are transferred to secondary
values to perform injections by a test set. Primary values are transferred to
secondary values by taking into account the CT ratio and the VT ratio (respectively
9000/1 A and 13.8/0.1 kV in the example).
The magnitude of the secondary voltages, that are related to the points RE and SE
of the R-X plane, needs to be checked.
RE (R
, X
):
FwdR
FwdX
V
VT s
,
V
V
11931
=
×
=
t FwdZs
,
t FwdZ
,
V
VT p
,
EQUATION14054 V1 EN-US
SE (R
, X
):
RvsR
RvsX
V
VT s
,
V
V
5899
=
×
=
t RvsZs
,
t RvsZ
,
V
VT p
,
EQUATION14055 V1 EN-US
The tests, which are described in this section, may require voltages that have
magnitude equal to 110% of the previous values. The continuous permissive
overload voltage of the protection voltage channels of the TRM module is 420 V;
so the previous voltages may be applied to the analog channels of the IED
continuously. Limitations may be related to the available test set; the current I
8 19
.
0 9522 0 078
.
.
=
×
=
100
59 33
.
0 9522 0 565
.
.
=
×
=
100
0 29
.
0 9522 0 003
.
.
=
×
=
100
29 6
.
0 9522 0 282
.
.
=
×
=
100
2
2
X
I
0 078
.
0 565
+
×
=
+
FwdX
t
2
2
X
I
0 003
.
0 282
+
×
=
+
RvsX
t
0 1
.
86 45
.
V
×
=
13 8
.
0 1
.
42 75
.
V
×
=
13 8
.
Section 11
2
.
20918 0 570 0 20918 11931
.
×
=
×
2
.
20918 0 282 2 20918 5899
.
×
=
×
(Equation 8)
(Equation 9)
(Equation 10)
(Equation 11)
V
=
(Equation 12)
V
=
(Equation 13)
(Equation 14)
(Equation 15)
was
t
149