Setting The Tcp/Udp Client Communication - ABB RET670 Commissioning Manual

Relion 670 series, transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 165-UEN A
Establishing connection and verifying the IEEE C37.118/1344 communication
9.4
Transformer protection RET670 2.2 IEC
Commissioning manual

Setting the TCP/UDP client communication

As an example of a TCP/UDP client, the openPDC tool (PMU Connection Tester
Ver. 4.2.12) from Grid Protection Alliance is used in this section. Install PMU
Connection Tester tool on a PC with Ethernet network adaptor available. The same
PC used for PCM600 can be used to install the PMU Connection Tester tool.
IEC140000133 V1 EN-US
Figure 9:
PMU Connection Tester tool
The following steps explain how to set the PMU Connection Tester parameters in
order to establish an IEEE C37.118 connection with the PMU:
1.
Set the IP stack on PMU Connection Tester to IPv4. Note that the default IP
stack on PMU Connection Tester tool is IPv6.
Section 9
GUID-6CEE3261-D211-4051-8CA8-5840C27C560E v2
IEC140000133-1-en.vsd
75