Pr.45 Multi-function PHC Output Terminal (MO1)
Factory Setting d00
Units None
Settings d00 - d14
Pr.46 Multi-function Output Relay Contact RA-RC (NO), RB-RC (NC)
Factory Setting d07
Units None
Settings d00 - d14
Multi-function Output Program Values
Value Function
d00 AC drive operational
d01 Pre-set frequency attained
d02 Non-zero speed
d03 Over-torque detection
d04 Base Block (B.B.) indicator
d05 Low-voltage Detect Indicator
d06 AC Drive Control Mode
d07 Fault Indicator
Explanation:
1. d00: AC Drive Operational – The Multi-function Output Terminal contacts will be
"closed" when the AC drive is running or the FWD or REV command is executed.
2. d01: Pre-set Frequency Attained – The Multi-function Output Terminal contacts will
be "closed" when the AC drive reaches the specified operating frequency defined by
Pr.04.
3. d02: Zero-speed Indicator – The Multi-function Output Terminal contacts will be
"closed" when the AC drive output frequency is less than the minimum output
frequency.
4. d03: Over-torque Detection Indicator – The Multi-function Output Terminal contacts
will remain "closed" as long as over-torque is detected. Parameter Pr.61 programs
the Over-torque Detection Level. Pr.62 sets for the time limitation for over-torque
before the AC drive output is turned off.
5. d04: Base Block Indicator – The Multi-function Output Terminal contacts will always
be "closed" as long as the AC drive output is turned off.
6. d05: Low-voltage Detect Indicator – The Multi-function Output Terminal contacts will
be "closed" when the AC drive detects a low-voltage state.
VLT
Value Function
d08 Desired Frequency Attained
d09 PLC Program Running
d10 PLC Program Step Completed
d11 PLC Program Execution Completed
d12 PLC Program Execution Paused
d13 Terminal Count Value Reached
d14 Preliminary Counter Value Reached