Introduction
Reaction time for T37
-
Maximum reaction time: 20 ms
1
1
Reaction time = delay between de-energizing the STO
input and switching off the frequency converter output
bridge.
Data for EN ISO 13849-1
-
Performance Level "d"
-
MTTF
years
-
DC (Diagnostic Coverage): 90%
-
Category 3
-
Lifetime 20 years
Data for EN IEC 62061, EN IEC 61508, EN IEC 61800-5-2
-
SIL 2 Capability, SILCL 2
-
PFH (Probability of Dangerous failure per
Hour)=1E-10/h
-
SFF (Safe Failure Fraction) >99%
-
HFT (Hardware Fault Tolerance)=0 (1001
architecture)
-
Lifetime 20 years
Data for EN IEC 61508 low demand
-
PFDavg for one year proof test: 1E-10
-
PFDavg for three year proof test: 1E-10
-
PFDavg for five year proof test: 1E-10
No maintenance of the STO functionality is needed.
Security measures have to be taken by the user e.g. instal-
lation in a closed cabinet that is only accessible for skilled
personnel.
SISTEMA Data
Functional safety data is available via a data library for use
with the SISTEMA calculation tool from the IFA (Institute
for Occupational Safety and Health of the German Social
Accident Insurance), and data for manual calculation. The
library is permanently completed and extended.
1.6.1 Terminal 37 Safe Stop Function
The frequency converter is available with safe stop
functionality via control terminal 37. Safe stop disables the
control voltage of the power semiconductors of the
frequency converter output stage. This in turn prevents
generating the voltage required to rotate the motor. When
the Safe Stop (T37) is activated, the frequency converter
issues an alarm, trips the unit, and coasts the motor to a
stop. Manual restart is required. The safe stop function can
be used as an emergency stop for the frequency converter.
In normal operating mode when safe stop is not required,
use the regular stop function instead. When automatic
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
8
(Mean Time To Dangerous Failure): 14000
d
MG20M902 - VLT
®
VLT
AQUA Drive
Operating Instructions
restart is used, ensure the requirements of ISO 12100-2
paragraph 5.3.2.5 are fulfilled.
Liability Conditions
It is the responsibility of the user to ensure that qualified
personnel installs and operates the safe stop function:
•
•
•
User is defined as: integrator, operator, service technician,
maintenance technician.
Standards
Use of safe stop on terminal 37 requires that the user
satisfies all provisions for safety including relevant laws,
regulations and guidelines. The optional safe stop function
complies with the following standards.
•
•
•
•
•
•
The information and instructions of the instruction manual
are not sufficient for a proper and safe use of the safe stop
functionality. The related information and instructions of
the relevant Design Guide must be followed.
Protective Measures
•
•
•
•
®
is a registered Danfoss trademark
Read and understand the safety regulations
concerning health and safety/accident prevention
Understand the generic and safety guidelines
given in this description and the extended
description in the relevant Design Guide
Have a good knowledge of the generic and safety
standards applicable to the specific application
IEC 60204-1: 2005 category 0 – uncontrolled stop
IEC 61508: 1998 SIL2
IEC 61800-5-2: 2007 – safe torque off (STO)
function
IEC 62061: 2005 SIL CL2
ISO 13849-1: 2006 Category 3 PL d
ISO 14118: 2000 (EN 1037) – prevention of
unexpected startup
Qualified and skilled personnel are required for
installation and commissioning of safety
engineering systems
The unit must be installed in an IP54 cabinet or
in an equivalent environment. In special
applications a higher IP degree is required
The cable between terminal 37 and the external
safety device must be short circuit protected
according to ISO 13849-2 table D.4
When external forces influence the motor axis (for
example, suspended loads), additional measures
are required (for example, a safety holding brake)
to eliminate potential hazards