No. Parameter
Function
Name
Explanation
13
Deceleration time 2 d0.1 - d600. sec
14
S-curve
S-curve
15
Jog Operation Jog acel/decel time d0.1 - d600. sec
16
Setting
Jog frequency
17
Multi-step
Multi-step speed 1 d0.0 - d400. Hz
18
Operation
Multi-step speed 2 d0.0 - d400. Hz
19
Speeds
Multi-step speed 3 d0.0 - d400. Hz
20
Multi-step speed 4 d0.0 - d400. Hz
21
Multi-step speed 5 d0.0 - d400. Hz
22
Multi-step speed 6 d0.0 - d400. Hz
23
Multi-step speed 7 d0.0 - d400. Hz
24
REV run
REV run inhibit
inhibit
25
Over-volt Stall Over-voltage stall
Prevention
prevention
26
Over-current
Over-current stall
Stall
prevention (during
Prevention
acceleration)
27
Over-current stall
prevention (during
operation)
28
DC Braking
DC braking current d0.0 - d100%
29
DC braking time
during start-up
30
DC braking time
during stopping
31
DC braking start-up d0.0 - d60.0 Hz
frequency
32
Momentary
Momentary power
Power Loss
loss operation
Protection
mode selection
VLT
Parameter
Value
d00 - d07
d0.1 - d400. Hz
d00:REV run enable
d01:Rev run disable
d00:Disable over-volt stall prevent
d01:Enable over-volt stall prevent
d50 - d200%
d50 - d200%
d0.0 - d5.0 sec
d0.0 - d25.0 sec
d00:Operation stops after
momentary power loss
d01:Operation continues after
momentary power loss.
Speed search starts with the
frequency reference value.
d02:Operation continues after
momentary power loss.
Speed search starts with the
minimum frequency
63
®
MICRO
Factory
Setting
d10.0
d00
d1.0
d6.00
d0.00
d0.00
d0.00
d0.00
d0.00
d0.0
d0.0
d00
d01
d170
d170
d0.0
d0.0
d0.0
d0.0
d00

Hide quick links: