CHAPTER 5: SETTINGS
The phase instantaneous overcurrent element can be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication
Instantaneous Overcurrent (IOC) Element Response to Saturated Waveforms in UR Series Relays (GET-8400A).
— This setting enables and disables the phase instantaneous overcurrent protection element.
FUNCTION
— Selects the signal source for the phase instantaneous overcurrent protection element.
SOURCE
— Specifies the phase instantaneous overcurrent pickup level in per-unit values.
PICKUP
—Delays the assertion of the
DELAY
and relays.
— Specifies a delay for the reset of the phase instantaneous overcurrent element between the operate output
RESET DELAY
state and the return to logic 0 after the input passes outside the defined pickup range. This setting is used to ensure that
the relay output contacts are closed long enough to ensure reception by downstream equipment.
— Assertion of the operand assigned to this setting block's phase A of the phase instantaneous overcurrent
BLOCK A
element.
— Enables and disables the logging of phase instantaneous overcurrent events in the sequence of events recorder.
EVENTS
5.7.4 Neutral current
5.7.4.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) NEUTRAL CURRENT
NEUTRAL CURRENT
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
operands. It is used to achieve timing coordination with other elements
PHASE IOC OP
Figure 5-101: Phase instantaneous overcurrent 1 logic
NEUTRAL TOC 1
NEUTRAL TOC 2
NEUTRAL TOC 3
NEUTRAL TOC 4
NEUTRAL TOC 5
NEUTRAL TOC 6
GROUPED ELEMENTS
See below
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
5
5-201