Omron CJ1G/H-CPU series Operation Manual page 316

Sysmac cj series
Hide thumbs Also See for CJ1G/H-CPU series:
Table of Contents

Advertisement

PLC Setup
7-1-2-8
Peripheral Port Tab Page
Host Link Settings
Communications Settings
Address in
Programming
Console
Word
Bit(s)
144
15
0: Standard*
1: PLC Setup (Cus-
tom)
Default: 0
Baud Rate (bps)
Address in
Programming
Console
Word
Bit(s)
145
0 to 7
00: 9,600 bps
01: 300 bps
02: 600 bps
03: 1,200 bps
04: 2,400 bps
05: 4,800 bps
06: 9,600 bps
07: 19,200 bps
08: 38,400 bps
09: 57,600 bps
0A: 115,200 bps
Default: 00
Format: Data Bits
Address in
Programming
Console
Word
Bit(s)
144
3
0: 7 bits
1: 8 bits
Default: 0
Format: Stop Bits
Address in
Programming
Console
Word
Bit(s)
144
2
0: 2 bits
1: 1 bit
Default: 0
The following settings are valid when pin 4 on the DIP switch on the CPU Unit
is ON.
Settings
*The default settings are for 1 start bit, 7
data bits, even parity, 2 stop bits, and a
baud rate of 9,600 bps.
Settings
This setting is valid only when the communi-
cations mode is set to the Host Link mode.
These settings are also valid only when the
Peripheral Port Settings Selection is set to
1: PLC Setup.
Settings
These settings are valid only when the com-
munications mode is set to Host link.
These settings are also valid only when the
Peripheral Port Settings Selection is set to
1: PLC Setup.
Settings
These settings are valid only when the com-
munications mode is set to Host link.
These settings are also valid only when the
Peripheral Port Settings Selection is set to
1: PLC Setup.
Function
Function
Function
Function
Section 7-1
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
283