Wiring
Electric Wires
Crimp Terminals
Wiring
242
The following wire gauges are recommended.
Terminal Block Connector
18-terminal
Note The current capacity of electric wire depends on factors such as the ambient
temperature and insulation thickness as well as the gauge of the conductor.
The terminals on the I/O Unit are M3, self-raising terminals with screws. Use
crimp terminals for wiring. Do not connect bare stranded wires directly to ter-
minals. Tighten the terminal block screws to the torque of 0.5 N·m. Use crimp
terminals (M3) having the dimensions shown below.
6.2 mm max.
Do not remove the protective label from the top of the Unit until wiring has
been completed. This label prevents wire strands and other foreign matter
from entering the Unit during wiring procedures. (Remove the label after wir-
ing has been completed to allow air circulation needed for cooling.)
During wiring
• Wire the Units so that they can be easily replaced. In addition, make sure
that the I/O indicators are not covered by the wiring.
• Do not place the wiring for I/O Units in the same duct or raceway as power
lines. Inductive noise can cause errors in operation.
• Tighten the terminal screws to the torque of 0.5 N·m.
• The terminals have screws with self-raising pressure plates. Connect the
lead wires to the terminals as shown below.
AWG 22 to 18 (0.32 to 0.82 mm
After wiring
17.5 mm
Screw (M3 screw with
self-raising pressure plate)
Section 5-3
Wire Size
2
)
6.2 mm max.
Remove the label.