PLC Setup
Baud Rate
Address in
Programming
Console
Word
Bit(s)
161
00 to 07
00 Hex: 9,600 bps
01 Hex: 300 bps
02 Hex: 600 bps
03 Hex: 1,200 bps
04 Hex: 2,400 bps
05 Hex: 4,800 bps
06 Hex: 9,600 bps
07 Hex: 19,200 bps
08 Hex: 38,400 bps
09 Hex: 57,600 bps
0A Hex: 115,200 bps
Default: 00 Hex
Send Delay
Address in
Programming
Console
Word
Bit(s)
162
00 to 15
0000 to 270F Hex (0
to 99,990 ms)
Unit: 10 ms
Default: 0000
Start Code/End Code
Address in
Programming
Console
Word
Bit(s)
164
8 to 15
00 to FF
Default: 00
0 to 7
00 to FF
Default: 00
165
12
0: None
1: Code in 164
Default: 0
8 to 9
0: None
1: Code in 164
2: CR+LF
Default: 0
0 to 7
00: 256 bytes
01 to FF:
1 to 255 bytes
Default: 00
280
Settings
This setting is valid only in no-protocol
communications mode. Set the Standard/
Custom setting (word 160, bit 15) to 1 to
enable this setting.
Settings
When the TXD(236) instruction is executed,
data will be sent from the RS-232C after the
send delay set here has expired.
Settings
Start code: Set this start code only when the
start code is enabled (1) in bits 12 to 15 of
165.
End code: Set this end code only when the
end code is enabled (1) in bits 8 to 11 of
165.
Start code setting:
A setting of 1 enables the start code in 164
bits 8 to 15.
End code setting:
With a setting of 0, the amount of data being
received must be specified. A setting of 1
enables the end code in bits 0 to 7 of 164. A
setting of 2 enables an end code of CR+LF.
Set the data length to be sent and received
with no-protocol communications. The end
code and start code are not included in the
data length.
Set this value only when the end code set-
ting in bits 8 to 11 of 165 is "0: None."
This setting can be used to change the
amount of data that can be transferred at
one time by TXD(236) or RXD(235). The
default setting is the maximum value of 256
bytes.
Function
Function
Function
Section 7-1
Related
When set-
flags and
ting is read
words
by CPU Unit
A61902
At the next
(RS-232C
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61902
At the next
(RS-232C
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61902
At the next
(RS-232C
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)