1-10 Comparison To Cs-Series Plcs - Omron CJ1G/H-CPU series Operation Manual

Sysmac cj series
Hide thumbs Also See for CJ1G/H-CPU series:
Table of Contents

Advertisement

Comparison to CS-series PLCs

1-10 Comparison to CS-series PLCs

Item
Dimensions: Height x width
Unit connections
Maximum I/O capacity
Maximum program capacity
Maximum data memory (DM and
EM Areas combined)
Instructions system
I/O memory
PLC Setup
Cyclic task functionality
Interrupt tasks
Programming Devices
Basic instructions 0.02 µs min.
Instruction
execution
Special instruc-
time
tions
Overhead time
Mounting
Inner Boards
Special I/O Units and CPU Bus
Units
CPU Rack mounting positions
Expansion Rack mounting posi-
tions
Expansion Racks
Maximum number of Expansion
Racks
Maximum total cable length to
Expansion Racks
Maximum number of Units
SYSMAC BUS Remote I/O
File Memory (Memory Cards or
EM Area)
Trace Memory
I/O allocation
74
The CS-series and CJ-series PLCs use the same architecture and are basi-
cally the same in terms of program structure (tasks), instruction system, I/O
memory, and other functionality. They do differ, however in that the CJ-series
PLCs have a different Unit structure, support different Units, do not support
Inner Boards, have different Expansion Racks, have a different I/O allocation
method, etc. These differences are outlined in the following table.
CJ-series PLCs, CJ1-H CPU Units
90 x 65 mm
Connected to each other via connectors.
End Cover connected to right end to indi-
cate end of Rack.
2,560 I/O points
120 Ksteps
256 Kwords
Same
Same
Same
Same
Same (Power OFF interrupt task, schedule interrupt tasks, I/O interrupt, and external
interrupt tasks)
CX-Programmer (versions 2.1 or higher) and Programming Consoles
0.06 µs min
0.3 ms
DIN Track (not mountable with screws)
Not supported.
Structure of allocations is the same.
Special I/O Units: 96 Units max. (restrictions on mounting positions)
CPU Bus Units: 16 Units max.
10 Units max. (11 Units or more will cause
an error)
10 Units max. (11 Units or more will cause
an error)
One I/O Control Unit required on CPU
Rack and one I/O Interface Unit required
on each Expansion Rack.
3
12 m
40
Not supported.
Same
Same
Automatic allocation from right to left
starting at Unit closest to CPU Unit and
then right to left on Expansion Racks.
Section 1-10
CS-series PLCs, CS1-H CPU Units
130 x 123 mm
Mounted to Backplanes.
5,120 I/O points
250 Ksteps
448 Kwords
DIN Track or screws
Supported.
3, 5, 8, or 10 slots
2, 3, 5, 8, or 10 slots
Either C200H or CS-series Expansion
Racks can be connected without an I/O
Control Unit or I/O Interface Units.
7
80
Supported.
Automatic allocation from right to left
starting at Unit closest to CPU Unit and
then right to left on Expansion Racks.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1m-cpu seriesCj1g-cpu series

Table of Contents