C Indicator; E Indicator; C/Q Indicator - Omron NX-ILM400 User Manual

Machine automation controller nx-series io-link master unit
Hide thumbs Also See for NX-ILM400:
Table of Contents

Advertisement

3-2-2

C Indicator

The meanings of the indicator are given below.
Color
Green
3-2-3

E Indicator

The meanings of the indicator are given below.
Color
Red
3-2-4

C/Q Indicator

The meanings of the indicator are given below.
Color
Yellow
NX-series IO-Link Master Unit User's Manual (W567)
Status
Lit
Initial processing is in progress or IO-Link communications are in prog-
ress during operation in IO-Link Mode.
Not lit
• IO-Link communications are stopped during operation in IO-Link
Mode.
• Operation is currently performed in SIO (DI) or SIO (DO) Mode.
• The port is disabled.
Status
Lit
A hardware error or other critical error has occurred.
Flashing at 1-s
There is an IO-Link communications error during operation in IO-Link
intervals
Mode.
Not lit
• There are no IO-Link communications errors during operation in
IO-Link Mode.
• Operation is currently performed in SIO (DI) or SIO (DO) Mode.
• The port is disabled.
Status
Lit
• The pin-2 input signal is ON during operation in IO-Link Mode.
• The I/O signal is ON during operation in SIO (DI) Mode or SIO (DO)
Mode.
Not lit
• The pin-2 input signal is OFF during operation in IO-Link Mode.
• The I/O signal is OFF during operation in SIO (DI) Mode or SIO (DO)
Mode.
• The port is disabled.
3 Part Names and Functions
Description
Description
Description
3