Periodic Inspection Items
Inspec-
No.
tion item
1
External
power sup-
ply
2
I/O power
supply
3
Ambient
environ-
ment
4
Installation
and wiring
NX-series IO-Link Master Unit User's Manual (W567)
Inspection details
Is the power supply voltage mea-
sured at the terminal block within
standards?
Is the power supply voltage mea-
sured at the I/O terminal block
within standards?
Is the ambient operating tem-
perature within standards?
Is the ambient operating humid-
ity within standards?
Is it subject to direct sunlight?
Is there an accumulation of dirt,
dust, salt, metal powder, etc.?
Is there water, oil, or chemical
sprays hitting the Controller?
Are there corrosive or flammable
gases in the area of the Control-
ler?
Is the Unit subject to shock or
vibration?
Are there noise sources near the
Controller?
Are the DIN track mounting
hooks for each NX Unit securely
locked?
Are the cable connectors fully
inserted and locked?
Are there any loose screws on
the End Plates (PFP-M)?
Are the NX Units connected to
each other along the hookup
guides and inserted until they
touch the DIN track?
Are there any damaged external
wiring cables?
8 Inspection and Maintenance
Criteria
Within the power supply
Use a voltage tester to check the power
voltage range
supply at the terminals. Take necessary
steps to bring the power supply within the
power supply voltage range.
Voltages must be within
Use a voltage tester to check the power
I/O specifications of each
voltage at the terminals. Take necessary
NX Unit.
steps to bring the I/O power supply within
NX Unit standards.
0 to 55°C
Use a thermometer to check the tem-
perature and ensure that the ambient
operating temperature remains within the
allowed range of 0 to 55°C.
Relative humidity must be
Use a hygrometer to check the humidity
10% to 95% with no con-
and ensure that the ambient operating
densation.
humidity remains between 10% and
95%.
Make sure that condensation does not
occur due to rapid changes in tempera-
ture.
Not in direct sunlight
Protect the Controller if necessary.
No accumulation
Clean and protect the Controller if neces-
sary.
No spray
Clean and protect the Controller if neces-
sary.
No spray
Check by smell or use a sensor.
Vibration resistance and
Install cushioning or other vibration and
shock resistance must be
shock absorbing equipment if necessary.
within specifications.
No significant noise
Either separate the Controller and noise
sources
source, or protect the Controller.
No looseness
Securely lock the DIN track mounting
hooks.
No looseness
Correct any improperly installed connec-
tors.
No looseness
Tighten loose screws with a Phillips-head
screwdriver.
You must connect and fix
Connect the NX Units to each other
the NX Units to the DIN
along the hookup guides and insert them
track.
until they touch the DIN track.
No visible damage
Check visually and replace cables if nec-
essary.
Correction
8 - 3