No/Nc Dual Eol 1K - Tyco iSTAR Ultra Installation And Configuration Manual

Door controller
Table of Contents

Advertisement

Table 6-8: Supervision Modes, continued
Mode
Casi-Rusco
1K Double NC (
Casi-Rusco
1K Double NO (
Simplex
5K Double NC (
)
Simplex
5K Double NO (
)
Andover
10K Double NC (
)
Andover
10K Double NO (
)
4.02K/8.04K Triple NC
Atlantek
(
)

NO/NC Dual EOL 1K

Figure 6-15
on page 6-19 shows the traditional Software House method of supervision where
1K
is considered Secure and 500
different for NO and NC.
Comment
)
Serial and Parallel Resistors
Normal = 1K
Alert = 2K
)
Parallel and Serial Resistors
Normal = 2K
Alert = 1K
Serial and Parallel Resistors
Normal = 5K
Alert = 10K
Parallel and Serial Resistors
Normal = 10K
Alert = 5K
Normal = 5K
Alert = 10K
Normal = 10K
Alert = 5K
Normal = 4.02K, Tamper = 10.06K
Alert = 8.04K, Tamper + Alarm = 14.08K
or
are considered Alert. Notice that the wiring is


Figure 6-15: NO / NC Dual EOL 1K
For UL Listed products,
burglar alarms must be supervised.
iSTAR Ultra Installation and Configuration Guide