Additional Power Requirements - Tyco iSTAR Ultra Installation And Configuration Manual

Door controller
Table of Contents

Advertisement

Power Requirements

Additional Power Requirements

4–4
iSTAR Ultra Installation and Configuration Guide
Table 4-3: iSTAR Ultra Wall Mount Ratings, continued
Voltage
Current
(Vdc)
(A)
12
9.49
12
10.49
12
15.49
12
18.99
12
23.49
12
27.99
12
29.49
Lock 1 and 2 Power Ratings:
0 - 30
4.5
0 - 30
6
0 - 30
7.5
ac0 - 30
9
0 - 30
12
0 - 30
15.75
0 - 30
19.5
0 - 30
24
An external over-current protection device (i.e. circuit breaker) must be installed in a
secure location readily accessible to a service person.
Local External
Circuit Breaker
Rating (A)
System Description
12
(1) GCM with (2) RS-485 Loads & (1) ACM with
(3) Wiegand/RS485/Aux load
15
(1) GCM with (2) RS-485 Loads & (1) ACM with
(4) Wiegand/RS485/Aux load
20
(1) GCM with (2) RS-485 Loads & (1) ACM with
(7) Wiegand/RS485/Aux load
25
(1) GCM with (2) RS-485 Loads & (2) ACM with
(9) Wiegand/RS485/Aux load
30
(1) GCM with (2) RS-485 Loads & (2) ACM with
(12) Wiegand/RS485/Aux load
35
(1) GCM with (2) RS-485 Loads & (2) ACM with
(15) Wiegand/RS485/Aux load
40
(1) GCM with (2) RS-485 Loads & (2) ACM with
(16) Wiegand/RS485/Aux load
-
(6) Locks
7.5
(8) Locks
10
(10) Locks
12
(12) Locks
15
(16) Locks
20
(21) Locks
25
(26) Locks
30
(32) Locks