Wiegand Connections
J16, J25, J31, J78, J79, J80, J22, J28
Direct Wiegand signaling read head connections are shown in
The data line maximum lengths are:
18 AWG - 500 feet
20 AWG - 300 feet
22 or 24 AWG - 200 feet
Table 6-1
on page 6-9 describes the pinouts.
Wiegand Port
Pin Number
Figure 6-7: Wiegand Readers
Table 6-1: Wiegand Port Pinouts
Signal/Function
1
2
GND - PWR Return
3
Data 0 - Wiegand Input
4
Data 1 - Wiegand Input
5
Red LED - active low
6
Yellow LED - active low
7
Green LED -active low
8
Beeper - active low
iSTAR Ultra Installation and Configuration Guide
Figure 6-7
Power +12 Vdc
Access Control Module
on page 6-9.
6–9