Table 6-8: Supervision Modes, continued
Mode
5K Dual NO/NC
5K Single Series NC
5K Single Parallel NO
10K Dual NO/NC
10K Single Series NC
10K Single Parallel NO
Unsupervised NC
Unsupervised NO
1K/2K Double NC (MDI)
6.8K/18K Double NC
(Infographics)
6.8K/18K Double NO
Infographics)
200/10K Double NC
(Infographics)
200/10K Double NO
(Infographics)
Comment
Wire with Parallel/Serial for NO and Serial/Parallel for NC.
Normal = 5K
NO Alert = 2.5K
NC Alert = 10K
Series Resistor
Normal = 5K
Alert = open (∞ Ω)
Parallel Resistor
Normal = 5K
Alert = short (0 Ω)
Wire with Parallel/Serial for NO and Serial/Parallel for NC.
Normal = 10K
NO Alert = 5K
NC Alert = 20K
Series Resistor
Normal = 10K
Alert = open (∞ Ω)
Parallel Resistor
Normal = 10K
Alert = short (0 Ω)
No Resistors
Normal = short (0 Ω)
Alert = open (∞ Ω)
No Resistors
Normal = open (∞ Ω)
Alert = short (0 Ω)
Serial and Parallel Resistors
Normal = 1K
Alert = 3K
Serial and Parallel Resistors
Normal = 6.8K
Alert = 24.8K
Parallel and Serial Resistors
Normal = 24.8K
Alert = 6.8K
Serial and Parallel Resistors
Normal = 196
Alert = 10K
Parallel and Serial Resistors
Normal = 10K
Alert = 196