Figure 4-17. Wire Tie Anchors; Figure 4-18. Building Alarm Terminal Block Connector Assignments; Table 4-1. Building Alarm Connections And Wire Terminations - Eaton 93PM-L Installation And Operation Manual

20-120 kw (208v)
Hide thumbs Also See for 93PM-L:
Table of Contents

Advertisement

UPS System Installation

Figure 4-17. Wire Tie Anchors

Table 4-1. Building Alarm Connections and Wire Terminations

Terminal Name
10
Building Alarm 1
9
Building Alarm 1 Return
8
Building Alarm 2
7
Building Alarm 2 Return
6
Building Alarm 3
5
Building Alarm 3 Return
4
Building Alarm 4
3
Building Alarm 4 Return
2
Building Alarm 5
1
Building Alarm 5 Return
Building Alarm 5 Return
Building Alarm 5
Building Alarm 4 Return
Building Alarm 4

Figure 4-18. Building Alarm Terminal Block Connector Assignments

4-24
Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02
Description
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Input: Programmable UPS alarm, activated by a
remote dry contact closure
UPS Building Alarms
1
2
3
4
5
6
Wire Tie Anchors
Recommended
Wire Size
Twisted Pair Wires
#18 AWG
Twisted Pair Wires
#18 AWG
Twisted Pair Wires
#18 AWG
Twisted Pair Wires
#18 AWG
Twisted Pair Wires
#18 AWG
7
8
9 10
Building Alarm 1
Building Alarm 1 Return
Building Alarm 2
Building Alarm 2 Return
Building Alarm 3
Building Alarm 3 Return
www.eaton.com/powerquality
Size of Pressure
Termination
Tightening Torque
2 lb in
#1430 AWG
(0.22-0.25 Nm)
2 lb in
#1430 AWG
(0.22-0.25 Nm)
2 lb in
#1430 AWG
(0.22-0.25 Nm)
2 lb in
#1430 AWG
(0.22-0.25 Nm)
2 lb in
#1430 AWG
(0.22-0.25 Nm)

Advertisement

Table of Contents
loading

Table of Contents