UPS System Installation
Figure 4-17. Wire Tie Anchors
Table 4-1. Building Alarm Connections and Wire Terminations
Terminal Name
10
Building Alarm 1
9
Building Alarm 1 Return
8
Building Alarm 2
7
Building Alarm 2 Return
6
Building Alarm 3
5
Building Alarm 3 Return
4
Building Alarm 4
3
Building Alarm 4 Return
2
Building Alarm 5
1
Building Alarm 5 Return
Building Alarm 5 Return
Building Alarm 5
Building Alarm 4 Return
Building Alarm 4
Figure 4-18. Building Alarm Terminal Block Connector Assignments
4-24
Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02
Description
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Input: Programmable UPS alarm, activated by a
remote dry contact closure
UPS Building Alarms
1
2
3
4
5
6
Wire Tie Anchors
Recommended
Wire Size
Twisted Pair Wires
#18 AWG
Twisted Pair Wires
#18 AWG
Twisted Pair Wires
#18 AWG
Twisted Pair Wires
#18 AWG
Twisted Pair Wires
#18 AWG
7
8
9 10
Building Alarm 1
Building Alarm 1 Return
Building Alarm 2
Building Alarm 2 Return
Building Alarm 3
Building Alarm 3 Return
www.eaton.com/powerquality
Size of Pressure
Termination
Tightening Torque
2 lb in
#1430 AWG
(0.22-0.25 Nm)
2 lb in
#1430 AWG
(0.22-0.25 Nm)
2 lb in
#1430 AWG
(0.22-0.25 Nm)
2 lb in
#1430 AWG
(0.22-0.25 Nm)
2 lb in
#1430 AWG
(0.22-0.25 Nm)