List of Tables This page intentionally left blank. viii Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Power wiring is installed through the bottom of the cabinet with an optional sidecar available for top entry wiring. Figure 1-1 shows the Eaton 93PM-L 120 kW, Four Wire UPS and Figure 1-2 shows the Eaton 93PM-L 120 kW, Four Wire UPS with a left or right mounted top entry wiring sidecar.
Figure 1-1. Eaton 93PM-L UPS (120 kW, Four Wire) UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Figure 1-2. Eaton 93PM-L UPS (120 kW, Four Wire) with Left or Right Mounted Top Entry Wiring Sidecar Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
1.1.4 Energy Saver System Mode The 93PM-L Series UPS offers an Energy Saver System (ESS) mode that maximizes efficiency by eliminating unnecessary power conversion when the commercial power source is within acceptable voltage and frequency limits. In this mode, the UPS is actively monitoring the critical bus and instantly and seamlessly transitions to double-conversion mode (inverter online) if a commercial electrical power brownout, blackout, overvoltage, undervoltage, or out-of-tolerance frequency condition occurs.
UPS cabinet. Our manufacturing facility installs the sidecar can be installed on the left or right side of the UPS cabinet based on the order requirements. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
UPS from virtually any location within the facility, up to 300 feet from the UPS. Refer to the Eaton 93PM Remote Monitoring Device (RMD) Installation and Operation Manual, listed in paragraph 1.8, for additional information.
Introduction Using This Manual This manual describes how to install and operate the Eaton 93PM-L 120 kW, Four Wire UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation. In particular, be thoroughly familiar with the REPO procedure (see paragraph 6.3.16) or the LOAD OFF procedure (see paragraph 6.3.15).
(WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. For More Information Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate for the following additional information:...
Page 20
All other countries: Call your local service representative Please use the following e-mail address for manual comments, suggestions, or to report an error in this manual: E-ESSDocumentation@eaton.com Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors. Attempting to alter wiring can cause injury. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Page 22
Ne pas fumer près des accumulateurs. Ne pas produire de flamme ou d’étincelle dans la zone de l’accumulateur. Dissiper l'électricité statique de votre corps en touchant une surface reliée à la terre avant de toucher les accumulateurs. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
The system must be operated at an altitude no higher than 1500m (5000 ft) without derating. For additional assistance with high altitude operation, contact an Eaton service representative (see paragraph 1.9). The system must be installed in a temperature and humidity controlled indoor area free of conductive contaminants.
Page 24
UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and may reduce or void the battery warranty. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
UPS Installation Plan and Unpacking The UPS ventilation requirements are shown in Table 3-1. To allow for future power upgrades, Eaton recommends using air conditioning or ventilation sized for the fully rated UPS kW frame size installed instead of the derated kW ordered. Sizing the site cooling infrastructure to be capable of cooling the maximum kW frame size will allow a full power rating upgrade without having to modify the infrastructure.
457 mm (18") minimum clearance for ventilation From Back of Cabinet with Top Exhaust None Required From Right Side of Cabinet None Required From Left Side of Cabinet None Required Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
UPS Installation Plan and Unpacking Right Side Front Dimensions are in millimeters [inches] Figure 3-1. UPS Cabinet Dimensions (Front and Right Side Views) Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
UPS with Left -Mounted Sidecar UPS with Right -Mounted Sidecar Dimensions are in millimeters [inches] Figure 3-4. UPS Cabinet with Left-Mounted or Right-Mounted Sidecar Dimensions (Front Views) Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Refer to national and local electrical codes for acceptable external wiring practices. To allow for future power upgrades, Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed instead of the derated kW ordered.
Page 37
If the maintenance bypass solution being installed does not provide such functionality, DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass. The Eaton 93PM-L UPS provides backfeed detection and protection through a shunt trip mechanism of the bypass input breaker.
(each) DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate DC Input from External Battery (Standalone Eaton...
(each) DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate DC Input from External Battery (Standalone Eaton...
UPS Installation Plan and Unpacking Table 3-6. Input/Output Ratings and External Wiring Recommendations for the Eaton 93PM-L 120 - (Single Input Bypass 220/208) Units Rating 50/60 Hz Basic Unit Rating (See Note) Input and Output Voltage Volts 220/208 220/208 220/208...
Table 3-8 for supplied external wiring terminal hardware, and Table Table 3-9 for recommended installation parts and tools not supplied by Eaton. Figure 4-8 and Figure 4-12 show the location of the UPS power cable terminals. Table 3-7. UPS External Power Cable Terminations for the Eaton 93PM-L 120 Bus Landings Tightening Torque...
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table 3-11 in accordance with the NEC, ANSI/NFPA 70. 3-22 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac. Alarm relay wiring should be a minimum of 18 AWG (recommended 18 AWG). 3-24 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 3-2 for cabinet weight).
UPS Installation Plan and Unpacking UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Figure 3-11. UPS Cabinet with Left-Mounted or Right-Mounted Top Entry Wiring Sidecar as Shipped on Pallet Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 3-27...
Page 50
UPS Installation Plan and Unpacking This page intentionally left blank. 3-28 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Figure 4-1. Place a floor protector from the parts kit underneath each jacking bolt, and screw the bolts down against them. The floor protectors protect the floor from being marred by the jacking bolts. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Pallet Skid (2 places front) (2 places rear) Figure 4-1. Removing the Pallet Skids and Supports – Eaton 93PM-L UPS WARNING Do not remove or loosen the cabinet mounting or cabinet support bolts until instructed. Loosen, but do not remove, the skid mounting bolts holding the pallet skids to the front and rear supports, and to the left and right side supports (see Figure 4-1).
(2 places front) (2 places rear) Figure 4-2. Removing the Sidecar Pallet Skids and Supports – Eaton 93PM-L UPS with Sidecar Turn each jacking bolt consecutively, two full turns, until the pallet skids clear the floor by approximately 3 mm (1/8").
Page 54
31. Using the retained cabinet mounting bolts, install the floor mounting brackets to the front and rear of the UPS with the angle facing outward. 32. Secure the cabinet to the floor with customer-supplied hardware. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Large High Rate, listed in paragraph 1.8, for installation instructions. IMPORTANT If the Eaton 93PM-L UPS has a SIAC-B, the Integrated Battery Cabinet must be installed on the opposite side of the UPS away from the SIAC-B. After the IBC is installed, proceed to paragraph 4.4 to complete the wiring of the UPS.
See Figure 4-8 for UPS terminal locations. For a detailed view of the UPS and UPS with Sidecar (SIAC-B) terminal blocks, see Figures 4-8 and 4-9. Proceed to paragraph 4.5 "Battery Power Wiring" Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
For a detailed view of the UPS and UPS with Sidecar (SIAC-B) terminal blocks, see Figures 4-8, 4-9, and 4-10. Proceed to paragraph 4.5 "Battery Power Wiring" Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
See Figure 4-11for UPS terminal locations. For a detailed view of the UPS and UPS with Sidecar (SIAC-B) terminal blocks, see Figure 4-11. Proceed to paragraph 4.5 "Battery Power Wiring" Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
For a detailed view of the UPS and UPS with Sidecar (SIAC-B) terminal blocks, see Figures 4-8, 4-9, and 4-12. Proceed to paragraph 4.5 "Battery Power Wiring". 4-10 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Left Side View Right Side View Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Figure 4-7. UPS Inter-Cabinet Wiring Access Location Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-13...
Load (A, B, C, N) (See Figure 4-9 for detail.) AC Input to UPS Bypass (A, B, C, N) (See Figure 4-9 for detail.) Front Figure 4-8. Power Terminal Locations 4-14 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8. See Figure 4-5, Figure 4-6, and Figure 4-7 for wiring access information, and Figure 4-8 for terminal locations.
Page 71
4.6.6; if wiring REPO connections, proceed to paragraph 4.7; otherwise, proceed to Step 16. 16. Close the UPS outside door and secure the latch. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-21...
UPS System Installation Minislot Communication Bays (See Figure 4-15 for detail.) Interface Terminals (See Figure 4-15 for detail.) Front Figure 4-14. Interface Terminal Locations 4-22 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Figure 4-20 for terminal assignments. Reinstall the sidecar front panel and secure with the retained hardware. Close the UPS outside door and secure the latch. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-25...
2 / 3 / 4 Breaker SIAC-B Aux COM - MIS 9 Aux NC - MIS 10 Front of UPS Figure 4-20. Sidecar TB1 and TB2 Terminal Locations 4-26 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
UPS building alarm terminals. See Figure 4-7 for UPS wiring access information, and Figure 4-14 and Figure 4-15 for UPS terminal locations. Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8, for...
UPS building alarm terminals. See Figure 4-5 for wiring access information, and Figure 4-14 and Figure 4-15 for UPS interface terminal locations. Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8, for battery cabinet wiring access information...
Page 79
UPS battery shunt trip terminals. See Figure 4-6 and Figure 4-7 for UPS wiring access information, and Figure 4-21 and Figure 4-22 for UPS terminal locations. Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8, for...
14. If wiring Minislot connections, proceed to paragraph 4.6.6; if wiring REPO connections, proceed to paragraph 4.7; otherwise, proceed to Step 15. 15. Close the UPS outside door and secure the latch. 4-32 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Remove the cabinet stiffener bar (see Figure 4-15) before installing or removing Minislot cards. Reinstall the bar after the procedure is completed. For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.9). To install wiring: If not already installed, install the LAN drop.
Remove the bottom interface entry conduit landing plate to drill or punch holes (see Figure 4-16). 10. Reinstall the interface entry plate and install the conduit. 4-34 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
REPO switch rating is 24 Vdc, 1A minimum. NOTE The REPO switch must be a latching-type switch not tied to any other circuits. Figure 4-26. Normally-Closed REPO Switch Wiring 4-36 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Eaton Customer Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) Air conditioning equipment is installed and operating correctly. The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) Adequate workspace exists around the UPS and other cabinets.
Page 89
UPS System Installation Notes Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-39...
Page 90
UPS System Installation This page intentionally left blank. 4-40 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Understanding UPS Operation UPS System Overview The Eaton 93PM-L UPS is a continuous-duty, solid-state, transformerless, three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load. The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated communication server, and digital signal processor (DSP) logic.
5.2.1 Modes The Eaton 93PM-L UPS supports a critical load in four different modes of operation: In Energy Saver System (ESS) mode, commercial AC power is supplied directly to the critical load through the internal bypass and transfers automatically to Normal mode (double-conversion on demand) if an abnormal condition is detected.
If the UPS suffers an internal failure and is configured for capacity, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Normal mode. Depending on the total load and the duration of the battery discharge, battery current limit alarms may be seen for a short time due to the current required to recharge the battery. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Single six UPM reverse transfer UPS with external battery See Figure 5-7 93PM-L 120-6 with 208 or 220 208 or 220 Single six UPM reverse transfer UPS with external battery Sidecar with Sidecar Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Figure 6-1 shows the control panel location on the front door of the UPS. For a description of the UPS control panel functions, and how to control and monitor UPS operation, see paragraph 6.2. Control Panel Door Latch Figure 6-1. UPS Controls and Indicators Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 6.3 for use of the operational controls. When the unit powers up, the screen displays the as shown in Figure 6-2. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
This message is also written to the Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Look at a log of UPS events (alarms, notices, and commands) (see paragraph 6.2.6) Monitor UPS operation (see paragraph 6.2.6) Set UPS parameters (see paragraph 6.2.6) Control UPS operation (see paragraphs 6.2.6 and 6.2.8) Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation of the operating status of the system. Figure 6-4. Main Menu and Mimic Screen Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Tap the STATISTICS tab on the main menu navigation bar to display a summary of UPS statistics (see Figure 6-13). Statistics Details Tap the desired statistic button to display the detailed statistic screen. Controls See paragraph 6.2.8 for details. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Enter the password using the keypad displayed and tap the return key (see Figure 6-15). Level 1 default password is 1111. Settings Level 2 default password is 0101. Sign in is complete. Tap continue to return to previous screen. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-11...
UPS Operating Instructions Single UPS Operation NOTE 1 If an Integrated Battery Cabinet (IBC) is installed, refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8, for IBC battery breaker location.
The UPM rectifier and inverter turn on. When the inverter reaches full voltage, the UPS is ready to transfer to the Double Conversion mode and supply the critical load. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Tap the EAA CONTROLS tab on the secondary Control menu navigation bar. The EAA CONTROLS screen is displayed. Tap the DISABLE ESS button. The UPS transfers to Double Conversion mode. The NORMAL status indicator is illuminated. 6-18 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Tap the SHUT DOWN MODULE button. The UPM status indicates SHUTDOWN. The power module is turned off. The remaining UPMs continue to supply the critical load. Logic power remains on. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-19...
Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Tap the TURN OFF CHARGER button. 6-20 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
To restart the UPS after using the LOAD OFF follow the procedure in paragraph 6.3.1 or 6.3.2. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-21...
Restart the UPS by following the procedure in paragraph 6.3.1 or 6.3.2. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. 6-22 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
IRC-MS installation guide. One input can be activated by a switch or dry contact. The voltage source is provided by the card, no external voltage source is needed. For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.8). Refer to the manual supplied with the Minislot card for user instructions.
It’s also powered by CA Technologies, bringing together the best in hardware and software. PredictPulse Service is included at no charge during the first year of Eaton 93PM-L UPS operation (warranty period) along with the required connectivity parts. Beyond that, it may be purchased with Eaton Support Agreements or as a standalone subscription after the initial warranty expires.
Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
Page 126
Communication This page intentionally left blank. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Each battery string is an energy source in itself. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service contact an Eaton service representative.
Ensure the operating environment is within the parameters specified in paragraph 3.2.1 and Chapter 9, “Product Specifications. ” Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated or the Normal status indicator is not illuminated, contact an Eaton service representative. 8.2.2 MONTHLY Maintenance Perform the following steps monthly: Monitor system parameters as described in paragraph 6.2, “Using the Control Panel”...
8.2.3 ANNUAL Maintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings. 8.2.4 BATTERY Maintenance Contact an Eaton service representative for battery maintenance.
Maintenance Training A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Customer Reliability Center (see paragraph 1.8).
Meets IEC 61000-4-2 Level 3 specifications. Withstands up to 4 kV contact Immunity pulse without damage and with no disturbance or adverse effect to the critical load. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
Page 134
Product Specifications This page intentionally left blank. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton.