Eaton 93PM-L Installation And Operation Manual

20-120 kw (208v)
Hide thumbs Also See for 93PM-L:
Table of Contents

Advertisement

®
Eaton
93PM-L UPS
20 – 120 kW (208V) UPS
Installation and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Eaton 93PM-L

  • Page 1 ® Eaton 93PM-L UPS 20 – 120 kW (208V) UPS Installation and Operation Manual...
  • Page 3 ® Eaton 93PM-L UPS 20 – 120 kW (208V) UPS Installation and Operation Manual...
  • Page 4 Schneider Electric. National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ©Copyright 2017 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 5: Table Of Contents

    Installing Battery Shunt Trip Interface Connections........4-28 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 6 6.3.16 Using the Remote Emergency Power-off Switch ......... 6-22 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 7 WARRANTY....................Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02...
  • Page 8 Table of Contents This page intentionally left blank. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 9 Figure 4-10. Eaton 93PM-L with SIAC-B (2-Breaker) Power Terminal Locations .......
  • Page 10 Air Filter Location ..............Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02...
  • Page 11 UPS External Power Cable Terminations for the Eaton 93PM-L 120 ......
  • Page 12: List Of Tables

    List of Tables This page intentionally left blank. viii Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 13: Introduction

    Power wiring is installed through the bottom of the cabinet with an optional sidecar available for top entry wiring. Figure 1-1 shows the Eaton 93PM-L 120 kW, Four Wire UPS and Figure 1-2 shows the Eaton 93PM-L 120 kW, Four Wire UPS with a left or right mounted top entry wiring sidecar.
  • Page 14: Figure 1-1. Eaton 93Pm-L Ups (120 Kw, Four Wire)

    Figure 1-1. Eaton 93PM-L UPS (120 kW, Four Wire) UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Figure 1-2. Eaton 93PM-L UPS (120 kW, Four Wire) with Left or Right Mounted Top Entry Wiring Sidecar Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 15: Control Panel

    1.1.4 Energy Saver System Mode The 93PM-L Series UPS offers an Energy Saver System (ESS) mode that maximizes efficiency by eliminating unnecessary power conversion when the commercial power source is within acceptable voltage and frequency limits. In this mode, the UPS is actively monitoring the critical bus and instantly and seamlessly transitions to double-conversion mode (inverter online) if a commercial electrical power brownout, blackout, overvoltage, undervoltage, or out-of-tolerance frequency condition occurs.
  • Page 16: Options And Accessories

    UPS cabinet. Our manufacturing facility installs the sidecar can be installed on the left or right side of the UPS cabinet based on the order requirements. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 17: Monitoring And Communication

    UPS from virtually any location within the facility, up to 300 feet from the UPS. Refer to the Eaton 93PM Remote Monitoring Device (RMD) Installation and Operation Manual, listed in paragraph 1.8, for additional information.
  • Page 18: Using This Manual

    Introduction Using This Manual This manual describes how to install and operate the Eaton 93PM-L 120 kW, Four Wire UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation. In particular, be thoroughly familiar with the REPO procedure (see paragraph 6.3.16) or the LOAD OFF procedure (see paragraph 6.3.15).
  • Page 19: Symbols, Controls, And Indicators

    (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. For More Information Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate for the following additional information:...
  • Page 20 All other countries: Call your local service representative Please use the following e-mail address for manual comments, suggestions, or to report an error in this manual: E-ESSDocumentation@eaton.com Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 21: Safety Warnings

    ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors. Attempting to alter wiring can cause injury. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 22 Ne pas fumer près des accumulateurs. Ne pas produire de flamme ou d’étincelle dans la zone de l’accumulateur. Dissiper l'électricité statique de votre corps en touchant une surface reliée à la terre avant de toucher les accumulateurs. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 23: Ups Installation Plan And Unpacking

    The system must be operated at an altitude no higher than 1500m (5000 ft) without derating. For additional assistance with high altitude operation, contact an Eaton service representative (see paragraph 1.9). The system must be installed in a temperature and humidity controlled indoor area free of conductive contaminants.
  • Page 24 UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and may reduce or void the battery warranty. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 25: Table 3-1. Air Conditioning Or Ventilation Requirements During Full Load Operation

    UPS Installation Plan and Unpacking The UPS ventilation requirements are shown in Table 3-1. To allow for future power upgrades, Eaton recommends using air conditioning or ventilation sized for the fully rated UPS kW frame size installed instead of the derated kW ordered. Sizing the site cooling infrastructure to be capable of cooling the maximum kW frame size will allow a full power rating upgrade without having to modify the infrastructure.
  • Page 26: Table 3-2. Ups Cabinet Weights

    Eaton 93PM-L 120 with 6 UPMs Installed 506 (1114) 475 (1047) 4 at 119 (262) Eaton 93PM-L 120 with 1 UPM Installed - Left-Mounted or Right-Mounted Top Entry Wiring Sidecar (no breakers) 457 (1007) 426 (940) 6 at 71 (157)
  • Page 27: Table 3-3. Ups Cabinet Clearances

    457 mm (18") minimum clearance for ventilation From Back of Cabinet with Top Exhaust None Required From Right Side of Cabinet None Required From Left Side of Cabinet None Required Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 28: Figure 3-1. Ups Cabinet Dimensions (Front And Right Side Views)

    UPS Installation Plan and Unpacking Right Side Front Dimensions are in millimeters [inches] Figure 3-1. UPS Cabinet Dimensions (Front and Right Side Views) Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 29: Figure 3-2. Ups Cabinet Dimensions (Top And Bottom Views)

    NOTE Top exhaust NOTE Rear exhaust configuration shown. configuration shown. Front Front Front Bottom Dimensions are in millimeters [inches] Figure 3-2. UPS Cabinet Dimensions (Top and Bottom Views) Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 30: Figure 3-3. Ups Cabinet Rear Floor Mounting Bracket Mounting Dimensions

    The UPS’ Front Floor Mounting Bracket’s mounting dimensions are identical to the Rear Floor Mounting Bracket dimensions. Figure 3-3. UPS Cabinet Rear Floor Mounting Bracket Mounting Dimensions Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 31: Figure 3-4. Ups Cabinet With Left-Mounted Or Right-Mounted Sidecar Dimensions (Front Views)

    UPS with Left -Mounted Sidecar UPS with Right -Mounted Sidecar Dimensions are in millimeters [inches] Figure 3-4. UPS Cabinet with Left-Mounted or Right-Mounted Sidecar Dimensions (Front Views) Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 32: Figure 3-5. Ups Cabinet With Left-Mounted Or Right-Mounted Sidecar Dimensions (Top And Bottom Views)

    UPS With Right-Mounted Sidecar UPS With Left-Mounted Sidecar Dimensions are in millimeters [inches] Figure 3-5. UPS Cabinet with Left-Mounted or Right-Mounted Sidecar Dimensions (Top and Bottom Views) 3-10 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 33: Figure 3-6. Ups Cabinet Center Of Gravity

    289 [11.4] 444 [978] Eaton 93PM-L 120 UPS - 6 UPMs Installed 1115 [43.9] 529 [20.8] 288 [11.3] 475 [1047] Figure 3-6. UPS Cabinet Center of Gravity Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 3-11...
  • Page 34: Figure 3-7. Ups Cabinet With Left-Mounted Or Right-Mounted Top Entry Wiring Sidecar Center Of Gravity

    Eaton 93PM-L 120 UPS - 6 UPMs Installed 1073 [42.2] 532 [20.9] 373 [14.7] 583 [1285] Figure 3-7. UPS Cabinet with Left-Mounted or Right-Mounted Top Entry Wiring Sidecar Center of Gravity 3-12 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 35: Figure 3-8. Ups Cabinet With Left-Mounted Or Right-Mounted Siac-B Center Of Gravity

    Eaton 93PM-L 120 UPS - 6 UPMs Installed 1032 [40.6] 558 [22.0] 426 [16.8] 715 [1577] Figure 3-8. UPS Cabinet with Left-Mounted or Right-Mounted SIAC-B Center of Gravity Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 3-13...
  • Page 36: Ups System Power Wiring Preparation

    Refer to national and local electrical codes for acceptable external wiring practices. To allow for future power upgrades, Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed instead of the derated kW ordered.
  • Page 37 If the maintenance bypass solution being installed does not provide such functionality, DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass. The Eaton 93PM-L UPS provides backfeed detection and protection through a shunt trip mechanism of the bypass input breaker.
  • Page 38: Table 3-4. Input/Output Ratings And External Wiring Recommendations For The Eaton 93Pm-L

    (each) DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate DC Input from External Battery (Standalone Eaton...
  • Page 39: Table 3-5. Input/Output Ratings And External Wiring Recommendations For The Eaton 93Pm-L

    (each) DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate DC Input from External Battery (Standalone Eaton...
  • Page 40: Table 3-6. Input/Output Ratings And External Wiring Recommendations For The Eaton 93Pm-L 120 - (Single Input Bypass 220/208)

    UPS Installation Plan and Unpacking Table 3-6. Input/Output Ratings and External Wiring Recommendations for the Eaton 93PM-L 120 - (Single Input Bypass 220/208) Units Rating 50/60 Hz Basic Unit Rating (See Note) Input and Output Voltage Volts 220/208 220/208 220/208...
  • Page 41: Table 3-7. Ups External Power Cable Terminations For The Eaton 93Pm-L 120

    Table 3-8 for supplied external wiring terminal hardware, and Table Table 3-9 for recommended installation parts and tools not supplied by Eaton. Figure 4-8 and Figure 4-12 show the location of the UPS power cable terminals. Table 3-7. UPS External Power Cable Terminations for the Eaton 93PM-L 120 Bus Landings Tightening Torque...
  • Page 42: Table 3-9. Recommended Installation Parts And Tools (Not Supplied By Eaton)

    54864BE 4/0 AWG 54866BE 250 MCM 54868BE 300 MCM 54870BE 350 MCM 54872BE 500 MCM 54876BE Manual Hydraulic Crimp Tool 14 Ton TBM14M Die Set 15506 3-20 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 43: Table 3-10. Power Cable Conduit Recommendations

    Eaton 93PM-L 120-5 (N+1) AC Output 208 Vac 2-1/2 (A, B, C, Neutral, Ground) 220 Vac Battery (Positive, Negative, Ground) NOTE Wires per conduit include neutral and ground wire. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 3-21...
  • Page 44: Table 3-11. Recommended Input And Bypass Circuit Breaker Ratings

    To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table 3-11 in accordance with the NEC, ANSI/NFPA 70. 3-22 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 45: Table 3-12. Recommended Output Circuit Breaker Ratings

    Eaton 93PM-L 120-4 80 kW 250A Eaton 93PM-L 120-5 (N+1) Eaton 93PM-L 120-5 100 kW 300A Eaton 93PM-L 120-6 (N+1) Eaton 93PM-L 120-6 120 kW 350A Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 3-23...
  • Page 46: Ups System Interface Wiring Preparation

    Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac. Alarm relay wiring should be a minimum of 18 AWG (recommended 18 AWG). 3-24 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 47: Inspecting And Unpacking The Ups Cabinets

    Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 3-2 for cabinet weight).
  • Page 48: Figure 3-10. Ups Cabinet As Shipped On Pallet

    UPS Installation Plan and Unpacking Figure 3-10. UPS Cabinet as Shipped on Pallet 3-26 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 49: Figure 3-11. Ups Cabinet With Left-Mounted Or Right-Mounted Top Entry Wiring Sidecar As Shipped On Pallet

    UPS Installation Plan and Unpacking UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Figure 3-11. UPS Cabinet with Left-Mounted or Right-Mounted Top Entry Wiring Sidecar as Shipped on Pallet Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 3-27...
  • Page 50 UPS Installation Plan and Unpacking This page intentionally left blank. 3-28 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 51: Ups System Installation

    Figure 4-1. Place a floor protector from the parts kit underneath each jacking bolt, and screw the bolts down against them. The floor protectors protect the floor from being marred by the jacking bolts. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 52: Figure 4-1. Removing The Pallet Skids And Supports - Eaton 93Pm-L Ups

    Pallet Skid (2 places front) (2 places rear) Figure 4-1. Removing the Pallet Skids and Supports – Eaton 93PM-L UPS WARNING Do not remove or loosen the cabinet mounting or cabinet support bolts until instructed. Loosen, but do not remove, the skid mounting bolts holding the pallet skids to the front and rear supports, and to the left and right side supports (see Figure 4-1).
  • Page 53: Figure 4-2. Removing The Sidecar Pallet Skids And Supports - Eaton 93Pm-L Ups With Sidecar

    (2 places front) (2 places rear) Figure 4-2. Removing the Sidecar Pallet Skids and Supports – Eaton 93PM-L UPS with Sidecar Turn each jacking bolt consecutively, two full turns, until the pallet skids clear the floor by approximately 3 mm (1/8").
  • Page 54 31. Using the retained cabinet mounting bolts, install the floor mounting brackets to the front and rear of the UPS with the angle facing outward. 32. Secure the cabinet to the floor with customer-supplied hardware. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 55: Figure 4-3. Removing The Sidecar Rear Shipping Bracket - Eaton 93Pm-L Ups With Left Mounted Sidecar

    UPS with SideCar Rear View with Top Vent Option UPS with SideCar Rear View with Rear Vent Option Figure 4-3. Removing the Sidecar Rear Shipping Bracket – Eaton 93PM-L UPS with Left Mounted Sidecar Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02...
  • Page 56: Integrated Battery Cabinet Installation

    Large High Rate, listed in paragraph 1.8, for installation instructions. IMPORTANT If the Eaton 93PM-L UPS has a SIAC-B, the Integrated Battery Cabinet must be installed on the opposite side of the UPS away from the SIAC-B. After the IBC is installed, proceed to paragraph 4.4 to complete the wiring of the UPS.
  • Page 57: Standalone Ups Or Ups With Pass-Through Sidecar (No Breakers)

    See Figure 4-8 for UPS terminal locations. For a detailed view of the UPS and UPS with Sidecar (SIAC-B) terminal blocks, see Figures 4-8 and 4-9. Proceed to paragraph 4.5 "Battery Power Wiring" Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 58: Ups With 2-Breaker Sidecar (Mbp And Mis)

    For a detailed view of the UPS and UPS with Sidecar (SIAC-B) terminal blocks, see Figures 4-8, 4-9, and 4-10. Proceed to paragraph 4.5 "Battery Power Wiring" Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 59: Ups With 4 -Breaker Sidecar (Rib, Bib, Mbp And Mis)

    See Figure 4-11for UPS terminal locations. For a detailed view of the UPS and UPS with Sidecar (SIAC-B) terminal blocks, see Figure 4-11. Proceed to paragraph 4.5 "Battery Power Wiring" Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 60: Ups With 4 -Breaker Sidecar (Rib, Bib, Mbp And Mis)

    For a detailed view of the UPS and UPS with Sidecar (SIAC-B) terminal blocks, see Figures 4-8, 4-9, and 4-12. Proceed to paragraph 4.5 "Battery Power Wiring". 4-10 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 61: Figure 4-5. Ups Conduit And Wire Entry Locations

    Bottom View Top Entry Conduit Landings for Customer Interface Wiring (Remove panels to drill or punch conduit holes.) Figure 4-5. UPS Conduit and Wire Entry Locations Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-11...
  • Page 62: Figure 4-6. Ups With Sidecar Conduit And Wire Entry Locations

    Bottom Entry Conduit Landing for DC Input (Remove panel to drill or punch conduit holes.) Figure 4-6. UPS with Sidecar Conduit and Wire Entry Locations 4-12 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 63: Figure 4-7. Ups Inter-Cabinet Wiring Access Location

    Left Side View Right Side View Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Figure 4-7. UPS Inter-Cabinet Wiring Access Location Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-13...
  • Page 64: Figure 4-8. Power Terminal Locations

    Load (A, B, C, N) (See Figure 4-9 for detail.) AC Input to UPS Bypass (A, B, C, N) (See Figure 4-9 for detail.) Front Figure 4-8. Power Terminal Locations 4-14 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 65: Figure 4-9. Eaton 93Pm-L Ups Power Terminal Detail

    DC Input from Battery + (E4) Phase B (E7) Phase A (E6) Cabinet Ground Terminals Cabinet Ground Post Ground Post Figure 4-9. Eaton 93PM-L UPS Power Terminal Detail Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-15...
  • Page 66: Figure 4-10. Eaton 93Pm-L With Siac-B (2-Breaker) Power Terminal Locations

    E6, E7 , E8, E12 LUGS AC INPUT TO BYPASS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Figure 4-10. Eaton 93PM-L with SIAC-B (2-Breaker) Power Terminal Locations 4-16 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 67: Figure 4-11. Eaton 93Pm-L With Siac-B (3-Breaker) Power Terminal Locations

    PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Figure 4-11. Eaton 93PM-L with SIAC-B (3-Breaker) Power Terminal Locations Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-17...
  • Page 68: Figure 4-12. Eaton 93Pm-L With Siac-B (4-Breaker) Power Terminal Locations

    PHASE C (E11) GROUND COMPRESSION LUGS ( 2X ) GROUND STUDS FOR CABINET TO CABINET WIRING Figure 4-12. Eaton 93PM-L with SIAC-B (4-Breaker) Power Terminal Locations 4-18 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 69: Figure 4-13. 93Pm-L Siac-B Rib Terminal Detail

    UPS System Installation PHASE C (RIB-5) AC INPUT TO RECTIFIER PHASE B (RIB-3) INPUT BREAKER PHASE A (RIB-1) Figure 4-13. 93PM-L SIAC-B RIB Terminal Detail Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-19...
  • Page 70: Battery Power Wiring

    Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8. See Figure 4-5, Figure 4-6, and Figure 4-7 for wiring access information, and Figure 4-8 for terminal locations.
  • Page 71 4.6.6; if wiring REPO connections, proceed to paragraph 4.7; otherwise, proceed to Step 16. 16. Close the UPS outside door and secure the latch. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-21...
  • Page 72: Figure 4-14. Interface Terminal Locations

    UPS System Installation Minislot Communication Bays (See Figure 4-15 for detail.) Interface Terminals (See Figure 4-15 for detail.) Front Figure 4-14. Interface Terminal Locations 4-22 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 73: Figure 4-15. Interface Terminal Detail

    Wire Tie Anchors (See Figure 4-17 for detail.) Bottom Access Interface Wiring Channel Bottom Entry Conduit Landings for Customer Interface Wiring Figure 4-16. Bottom Access Interface Wiring Location Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-23...
  • Page 74: Figure 4-17. Wire Tie Anchors

    Building Alarm 4 Return Building Alarm 2 Building Alarm 4 Building Alarm 2 Return Building Alarm 3 Building Alarm 3 Return Figure 4-18. Building Alarm Terminal Block Connector Assignments 4-24 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 75: Installing Sidecar Mis And Rib Breaker Monitoring Connections

    Figure 4-20 for terminal assignments. Reinstall the sidecar front panel and secure with the retained hardware. Close the UPS outside door and secure the latch. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-25...
  • Page 76: Figure 4-20. Sidecar Tb1 And Tb2 Terminal Locations

    2 / 3 / 4 Breaker SIAC-B Aux COM - MIS 9 Aux NC - MIS 10 Front of UPS Figure 4-20. Sidecar TB1 and TB2 Terminal Locations 4-26 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 77: Installing Battery Detect Interface Connections

    UPS building alarm terminals. See Figure 4-7 for UPS wiring access information, and Figure 4-14 and Figure 4-15 for UPS terminal locations. Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8, for...
  • Page 78: Installing Battery Shunt Trip Interface Connections

    UPS building alarm terminals. See Figure 4-5 for wiring access information, and Figure 4-14 and Figure 4-15 for UPS interface terminal locations. Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8, for battery cabinet wiring access information...
  • Page 79 UPS battery shunt trip terminals. See Figure 4-6 and Figure 4-7 for UPS wiring access information, and Figure 4-21 and Figure 4-22 for UPS terminal locations. Refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8, for...
  • Page 80: Figure 4-21. Battery Shunt Trip Locations

    UPS System Installation Shunt Trip Terminals (See Figure 4-22 for detail.) Figure 4-21. Battery Shunt Trip Locations 4-30 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 81: Figure 4-22. Battery Shunt Trip Terminal Detail

    2 lb in Output: Contacts used to open battery Twisted Pair Wires #18 #1430 AWG (0.22-0.25 Nm) breaker or disconnect 48 Vdc Battery Shunt Trip (+) Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-31...
  • Page 82: Generator Interface Connections

    14. If wiring Minislot connections, proceed to paragraph 4.6.6; if wiring REPO connections, proceed to paragraph 4.7; otherwise, proceed to Step 15. 15. Close the UPS outside door and secure the latch. 4-32 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 83: Installing Minislot Interface Connections

    Remove the cabinet stiffener bar (see Figure 4-15) before installing or removing Minislot cards. Reinstall the bar after the procedure is completed. For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.9). To install wiring: If not already installed, install the LAN drop.
  • Page 84: Installing A Repo Switch

    Remove the bottom interface entry conduit landing plate to drill or punch holes (see Figure 4-16). 10. Reinstall the interface entry plate and install the conduit. 4-34 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 85: Figure 4-23. Repo Switch

    18. Close the UPS outside door and secure the latch. UPS REPO Normally Closed EPO_A_B Normally Open EPO_A REPO Contacts REPO Contacts EPO_B GND-ISO Figure 4-24. REPO Terminal Block Connector Assignments Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-35...
  • Page 86: Figure 4-25. Normally-Open Repo Switch Wiring

    REPO switch rating is 24 Vdc, 1A minimum. NOTE The REPO switch must be a latching-type switch not tied to any other circuits. Figure 4-26. Normally-Closed REPO Switch Wiring 4-36 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 87: Initial Startup

    Eaton Customer Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 88: Installation Checklist

    Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) Air conditioning equipment is installed and operating correctly. The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) Adequate workspace exists around the UPS and other cabinets.
  • Page 89 UPS System Installation Notes Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 4-39...
  • Page 90 UPS System Installation This page intentionally left blank. 4-40 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 91: Understanding Ups Operation

    Understanding UPS Operation UPS System Overview The Eaton 93PM-L UPS is a continuous-duty, solid-state, transformerless, three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load. The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated communication server, and digital signal processor (DSP) logic.
  • Page 92: Single Ups

    5.2.1 Modes The Eaton 93PM-L UPS supports a critical load in four different modes of operation: In Energy Saver System (ESS) mode, commercial AC power is supplied directly to the critical load through the internal bypass and transfers automatically to Normal mode (double-conversion on demand) if an abnormal condition is detected.
  • Page 93: Energy Saver System Mode

    If the UPS suffers an internal failure and is configured for capacity, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 94: Bypass Mode

    UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 95: Battery Mode

    Normal mode. Depending on the total load and the duration of the battery discharge, battery current limit alarms may be seen for a short time due to the current required to recharge the battery. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 96: Single Ups Unit System Oneline Configurations

    Single six UPM reverse transfer UPS with external battery See Figure 5-7 93PM-L 120-6 with 208 or 220 208 or 220 Single six UPM reverse transfer UPS with external battery Sidecar with Sidecar Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 97: Figure 5-6. Eaton 93Pm-L 120-6 Ups System Oneline

    SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED. NOTE Callout letters A, B, C, and D map to Table 3-4 or Table 3-5. Figure 5-6. Eaton 93PM-L 120-6 UPS System Oneline Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 98: Figure 5-7. Eaton 93Pm-L 120-6 Ups With Sidecar System Oneline

    Understanding UPS Operation Figure 5-7. Eaton 93PM-L 120-6 UPS with Sidecar System Oneline Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 99: Ups Operating Instructions

    Figure 6-1 shows the control panel location on the front door of the UPS. For a description of the UPS control panel functions, and how to control and monitor UPS operation, see paragraph 6.2. Control Panel Door Latch Figure 6-1. UPS Controls and Indicators Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 100: Using The Control Panel

    The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 6.3 for use of the operational controls. When the unit powers up, the screen displays the as shown in Figure 6-2. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 101: Status Indicators

    This message is also written to the Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 102: Using The Lcd Touch Screen

    Look at a log of UPS events (alarms, notices, and commands) (see paragraph 6.2.6) Monitor UPS operation (see paragraph 6.2.6) Set UPS parameters (see paragraph 6.2.6) Control UPS operation (see paragraphs 6.2.6 and 6.2.8) Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 103: Using The Menu

    The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation of the operating status of the system. Figure 6-4. Main Menu and Mimic Screen Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 104: Display Menu Operation

    Tap the STATISTICS tab on the main menu navigation bar to display a summary of UPS statistics (see Figure 6-13). Statistics Details Tap the desired statistic button to display the detailed statistic screen. Controls See paragraph 6.2.8 for details. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 105: Figure 6-5. Typical Meters Summary Screen

    UPS Operating Instructions Figure 6-5. Typical Meters Summary Screen Figure 6-6. Typical Active Events Screen Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 106: Figure 6-7. Typical System Log Screen

    UPS Operating Instructions Figure 6-7. Typical System Log Screen Figure 6-8. Typical Settings User Screen Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 107: Figure 6-9. Typical Information Screen

    UPS Operating Instructions Figure 6-9. Typical Information Screen Figure 6-10. Typical About Screen Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 108: Figure 6-11. Typical Settings Configuration 1 Screen

    UPS Operating Instructions Figure 6-11. Typical Settings Configuration 1 Screen Figure 6-12. Typical Settings Configuration 2 Screen 6-10 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 109: Sign In

    Enter the password using the keypad displayed and tap the return key (see Figure 6-15). Level 1 default password is 1111. Settings Level 2 default password is 0101. Sign in is complete. Tap continue to return to previous screen. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-11...
  • Page 110: Figure 6-14. Sign In Password Screen

    UPS Operating Instructions Figure 6-14. Sign In Password Screen Figure 6-15. Sign In Keypad 6-12 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 111: System Controls

    Table 6-5. Typical System Status Messages Function Message Double Conversion; Bypass; ESS Bypass Off; On; Available Charger Charger Resting; Charger Figure 6-16. Typical System Control Screen Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-13...
  • Page 112: Figure 6-17. Typical Ups Control Screen

    UPS Operating Instructions Figure 6-17. Typical UPS Control Screen Figure 6-18. Typical UPM Select Screen 6-14 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 113: Figure 6-19. Typical Upm Control Screen

    UPS Operating Instructions Figure 6-19. Typical UPM Control Screen Figure 6-20. Typical EAA Control Screen Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-15...
  • Page 114: Single Ups Operation

    UPS Operating Instructions Single UPS Operation NOTE 1 If an Integrated Battery Cabinet (IBC) is installed, refer to the Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or the Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate, listed in paragraph 1.8, for IBC battery breaker location.
  • Page 115: Starting The Upms

    The UPM rectifier and inverter turn on. When the inverter reaches full voltage, the UPS is ready to transfer to the Double Conversion mode and supply the critical load. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 116: Transfer From Double Conversion To Bypass Mode

    Tap the EAA CONTROLS tab on the secondary Control menu navigation bar. The EAA CONTROLS screen is displayed. Tap the DISABLE ESS button. The UPS transfers to Double Conversion mode. The NORMAL status indicator is illuminated. 6-18 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 117: Transfer From Double Conversion Mode To Ess Mode

    Tap the SHUT DOWN MODULE button. The UPM status indicates SHUTDOWN. The power module is turned off. The remaining UPMs continue to supply the critical load. Logic power remains on. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-19...
  • Page 118: 6.3.11 Single Upm Restart

    Tap the CONTROLS tab on the main menu navigation bar. The Control screen is displayed. Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Tap the TURN OFF CHARGER button. 6-20 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 119: 6.3.14 Battery Test

    To restart the UPS after using the LOAD OFF follow the procedure in paragraph 6.3.1 or 6.3.2. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-21...
  • Page 120: 6.3.16 Using The Remote Emergency Power-Off Switch

    Restart the UPS by following the procedure in paragraph 6.3.1 or 6.3.2. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. 6-22 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 121: Figure 6-21. Repo Operation

    UPS Operating Instructions Activated Deactivated (Pushbutton locked into place.) (Unlock pushbutton to release.) Figure 6-21. REPO Operation Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality 6-23...
  • Page 122 UPS Operating Instructions This page intentionally left blank. 6-24 Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 123: Communication

    IRC-MS installation guide. One input can be activated by a switch or dry contact. The voltage source is provided by the card, no external voltage source is needed. For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.8). Refer to the manual supplied with the Minislot card for user instructions.
  • Page 124: Building Alarm Monitoring

    It’s also powered by CA Technologies, bringing together the best in hardware and software. PredictPulse Service is included at no charge during the first year of Eaton 93PM-L UPS operation (warranty period) along with the required connectivity parts. Beyond that, it may be purchased with Eaton Support Agreements or as a standalone subscription after the initial warranty expires.
  • Page 125: Installing Predictpulse

    Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
  • Page 126 Communication This page intentionally left blank. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 127: Ups Maintenance

    Each battery string is an energy source in itself. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service contact an Eaton service representative.
  • Page 128: Performing Preventive Maintenance

    Ensure the operating environment is within the parameters specified in paragraph 3.2.1 and Chapter 9, “Product Specifications. ” Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated or the Normal status indicator is not illuminated, contact an Eaton service representative. 8.2.2 MONTHLY Maintenance Perform the following steps monthly: Monitor system parameters as described in paragraph 6.2, “Using the Control Panel”...
  • Page 129: Annual Maintenance

    8.2.3 ANNUAL Maintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings. 8.2.4 BATTERY Maintenance Contact an Eaton service representative for battery maintenance.
  • Page 130: Installing Batteries

    Maintenance Training A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Customer Reliability Center (see paragraph 1.8).
  • Page 131: Product Specifications

    Eaton 93PM-L 120-6 105 kW 50/60 Hz Eaton 93PM-L 120-6 110 kW 50/60 Hz Eaton 93PM-L 120-6 115 kW 50/60 Hz Eaton 93PM-L 120-6 120 kW 50/60 Hz Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 132: Specifications

    1 Hz per second (default setting) Load Compatibility 0.8 pF Leading 0.8 pF Lagging Overload Capability <110% for 10 minutes <125% for 60 seconds <150% for 10 seconds >150% for 300 milliseconds Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 133: Ups Environmental

    Meets IEC 61000-4-2 Level 3 specifications. Withstands up to 4 kV contact Immunity pulse without damage and with no disturbance or adverse effect to the critical load. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 134 Product Specifications This page intentionally left blank. Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02 www.eaton.com/powerquality...
  • Page 135: Eaton 93Pm-L Ups (20-120 Kw, 208V) Installation And Operation Manual P-164000688-Rev 02 Www.eaton.com/Powerquality

    For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton.
  • Page 136 Eaton shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.
  • Page 138 *P-164000688 02* P-164000688 02...