Figure 3-7. UPS Cabinet with Left-Mounted or Right-Mounted Top Entry Wiring Sidecar Center of Gravity

3-12
Eaton 93PM-L UPS (20–120 kW, 208V) Installation and Operation Manual P-164000688—Rev 02
Weight and Center of Gravity with Side Mounted
Top Entry Wiring Sidecar (No Breakers)
Eaton 93PM-L 120 UPS - 1 UPM Installed
Eaton 93PM-L 120 UPS - 2 UPMs Installed
Eaton 93PM-L 120 UPS - 3 UPMs Installed
Eaton 93PM-L 120 UPS - 4 UPMs Installed
Eaton 93PM-L 120 UPS - 5 UPMs Installed
Eaton 93PM-L 120 UPS - 6 UPMs Installed
Eaton 93PM-L 120 UPS - 1 UPM Installed
Eaton 93PM-L 120 UPS - 2 UPMs Installed
Eaton 93PM-L 120 UPS - 3 UPMs Installed
Eaton 93PM-L 120 UPS - 4 UPMs Installed
Eaton 93PM-L 120 UPS - 5 UPMs Installed
Eaton 93PM-L 120 UPS - 6 UPMs Installed
Dimensions are in millimeters [inches]
Dimensions
A
B
C
mm (in)
mm (in)
mm (in)
936 [36.9]
517 [20.4]
486 [19.1]
953 [37.5]
521 [20.5]
493 [19.4]
976 [38.4]
524 [20.6]
500 [19.7]
1004 [39.5]
527 [20.7]
505 [19.9]
1037 [40.8]
530 [20.9]
511 [20.1]
1073 [42.2]
532 [20.9]
515 [20.3]
936 [36.9]
517 [20.4]
408 [16.1]
953 [37.5]
521 [20.5]
399 [15.7]
976 [38.4]
524 [20.6]
391 [15.4]
1004 [39.5]
527 [20.7]
385 [15.2]
1037 [40.8]
530 [20.9]
379 [14.9]
1073 [42.2]
532 [20.9]
373 [14.7]
www.eaton.com/powerquality
Installed Weight
kg (lb)
426 [940]
458 [1009]
489 [1078]
520 [1147]
552 [1216]
583 [1285]
426 [940]
458 [1009]
489 [1078]
520 [1147]
552 [1216]
583 [1285]