This chapter explains the types of errors that may occur when the D/A converter
module is used, and how to troubleshoot such errors.

8.1 Error Code List

If an error occurs in D/A converter module while writing to or reading data from the
PLC CPU, the applicable error code is written to buffer memory address 19 (Un\G19).
Error code
(decimal)
The setting is outside the output range setting that
can be made by the intelligent function module switch
10
of the GX Developer.
specified channel number.
111
Module error at startup.
The G.OGSTOR instruction was executed in the
1
161
offset/gain setting mode.
• The G.OGSTOR instruction was executed
consecutively.
2
162
• At the time of offset/gain setting, a set value was
written to the E
The G.OGSTOR instruction was executed for the
2
163
model that differs from the model for which the
G.OGLOAD instruction had been executed.
The offset value is equal to or greater than the gain
value at the time of user range setting or user range
2
40
restoration.
the error.
More than one channel was set at the same time
2
500
during offset/gain settings.
The specified digital value is outside the valid range.
2
60
indicates the channel number where the error
occurred.
The analog adjustment output in the offset/gain
2
700
setting mode is outside the specified value range.
(1) If more than one error occurs, the error code first detected by the D/A
(2) Error code 161 marked with
(3) Error code marked with
(4) The error is cleared at the time of mode switching.
8 - 1
Table 8.1 Error code list
Error description
indicates the incorrectly
2
PROM 26 or more times.
indicates the channel number causing
POINT
converter module is stored. No other error codes will be stored.
address 19 (Un\G19). It is written to the Completion status area, (S) + 1, of the
G(P).OGSTOR instruction.
(YF).
Processing
Reset to the correct parameter with GX Developer
parameter setting. (Refer to Section 4.5.)
Turn the power on and off again. If the error occurs
again, the module may be malfunctioning. Contact
the nearest distributor or branch office with a
description of the problem.
Do not execute the G.OGSTOR instruction in the
offset/gain setting mode.
• Execute the G.OGSTOR instruction only once for
one module.
• At the time of offset/gain setting, write a set value
only once at one time.
Execute the G.OGLOAD and G.OGSTOR
instructions for the same model.
Reset so that the offset value becomes smaller than
the gain value.
Set the correct value in Offset/gain setting mode and
offset/gain specification (buffer memory addresses
22, 23: Un\G22 and Un\G23).
Set a value that is within the valid range.
Change the contents of Offset/gain adjustment value
specification (buffer memory address 24 (Un\G24) so
that it is within the range from –3000 to 3000.
1 is not stored in Error code (buffer memory
2 can be cleared by turning on Error clear request
MELSEC-Q
8
8 - 1