Mitsubishi Electric Q62DAN User Manual Page 107

Melsecq series.
Hide thumbs

Advertisement

5 UTILITY PACKAGE (GX Configurator-DA)
5 - 30
(3) User range restoration
(a) Set "Voltage specified" or "Current specified" in the Setting value field of
CH
Pass data classification setting, and click the Execute test button.
When the setting is completed, the set data is displayed in the Current value
field of CH
(b) Set the values recorded in the setting value fields of CH
shipment settings offset/gain values/user range settings offset/gain values.
(c) Select all the setting value fields of CH
offset/gain values and User range settings offset/gain values, and click the
Execute test button.
When write is completed, the set values are displayed in the Current value
fields of CH
range settings offset/gain values.
(d) Change the Setting value field of Pass data write request to "Request", and
click the Execute test button.
Make sure that the indication in the Current value field of Pass data write
request changes from "Request" to "OFF" on completion of write.
Pass data classification setting.
Industrial shipment settings offset/gain values and CH
MELSEC-Q
Industrial
Industrial shipment settings
User
5 - 30