4 SETUP AND PROCEDURES BEFORE OPERATION
4 - 8
(3) For voltage output of the Q62DAN, Q64DAN, or Q68DAVN
1 Use a twisted two core shielded wire for the power wire.
2 If there is noise or ripples in the external wiring, connect a 0.1 to 0.47 F 25V
capacitor between the V+ terminal and COM.
(4) For current output of the Q62DAN, Q64DAN, or Q68DAIN
1 Use a twisted two core shielded wire for the power wire.
2 If there is noise or ripples in the external wiring, connect a 0.1 to 0.47 F 25V
capacitor between the I+ terminal and COM.