5 UTILITY PACKAGE (GX Configurator-DA)
5 - 28
Analog/Digital conversion: Select a conversion type shown below for confirming
Analog value: <When converted to a digital value>
<When converted to an analog value>
Digital value: <When converted to a digital value>
<When converted to an analog value>
POINT
The offset value is the analog output value (voltage or current) when a digital
entry value of 0 is set from the programmable controller CPU.
The gain value is the analog value (voltage or current) output when the digital
input value set from the programmable controller CPU is as follows:
4000 (When Normal resolution is selected)
12000 (When High resolution is selected)
(3) Command button
Range setting
Conversion
the correspondence between an analog value and a
digital value caused by the conversion characteristic.
Digital
Analog
Analog
Digital
Enter an analog value to be converted to a digital value
The analog value converted from a digital value is displayed.
The digital value corresponding to an entered analog value is
displayed.
Enter a digital value to be converted to an analog value.
The entered offset/gain value is determined, and the I/O
characteristic diagram is updated.
Conversion for the entered value is performed.
MELSEC-Q
5 - 28