Connecting The Smartlogger To A Split Emi - Huawei SmartLogger2000 User Manual

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

SmartLogger2000-(10-C, 11-C)
User Manual
Procedure
Step 1 Connect one end of the cable delivered with the EMI to the RS485 port of the EMI.
Step 2 Connect the other end of the cable to the COM port of the SmartLogger. For details, see
Connecting Cables to the Terminal Block on the COM
When connecting cables, ensure that the RS485+ and RS485- ports on the EMI respectively
connect to the COM+ and COM- ports on the SmartLogger.
----End
Follow-up Procedure
Disconnection can be performed in reverse order.

4.6.3 Connecting the SmartLogger to a Split EMI

Connecting to an EMI over a COM Port
The EMI used in Europe and Southeast Asia is composed of sensors, whose signals need to be
converted into RS485 signals (Modbus-RTU) over an extra analog-to-digital converter before
the sensors are connected to the SmartLogger.
The analog-to-digital converter should provide an RS485 port and support the standard
Modbus-RTU protocol. This section describes the connection between the SmartLogger and a
split EMI through the ADAM4117 that functions as an analog-to-digital converter.
The SmartLogger provides six RS485 communications ports. For the port descriptions, see
4.5.2 Connecting the SUN2000 Over
Figure 4-16
converter.
Issue Draft A (2017-02-15)
The EMI cannot be automatically identified. After connecting cables, log in to the embedded WebUI
and manually add the EMI. For details, see
and Comm.protocal to Modbus-RTU.
After adding an EMI, set its parameters. For details, see
Setting Running
Parameters. The EMI model is Jingzhou Yangguang (PC-4), Handan (RYQ-3),
Kipp&Zonen SMPx or Lufft WSx-UMB.
If the SmartLogger needs to be connected to an EMI and multiple SUN2000s, connect the EMI at
the end of the daisy chain, and verify that the port connected to the EMI has a unique
communications address. For the daisy chain connection, see
Connecting Multiple
SUN2000s.
shows how to connect the SmartLogger to a split EMI over an analog-to-digital
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Port.
7.10.7.1 Connecting
Connection over the COM Port
Daisy Chain Connection
RS485.
4 Electrical Connection
Devices. Set Device Type to EMI
in
7.7.5.2
in
4.5.4
4.3
48