SmartLogger2000-(10-C, 11-C)
User Manual
Paramete
No.
Description
r
9
Voltage
The standards of
rise
certain countries and
suppressio
regions require that
n reactive
the SUN2000 must
adjustment
generate a certain
point
amount of reactive
power when the output
voltage exceeds a
certain value.
10
Voltage
The standards of
rise
certain countries and
suppressio
regions require that
n active
the active power of the
derating
SUN2000 be derated
point
according to a certain
gradient when the
output voltage exceeds
a certain value.
11
Frequency
The SUN2000 triggers
change rate
protection when the
protection
power grid frequency
changes too fast.
12
Frequency
Specifies the
change rate
frequency change rate
protection
protection threshold.
point
13
Frequency
Specifies the
change rate
frequency change rate
protection
protection duration.
time
Soft start
Specifies the time for
14
time after
the power to gradually
grid failure
increase when the
SUN2000 restarts after
the power grid
recovers.
Issue Draft A (2017-02-15)
Default
Unit
Value
%
The default
value varies
depending on
the grid code.
%
The displayed
value prevails.
N/A
The default
value varies
depending on
Hz/s
the grid code.
The displayed
value prevails.
s
The default
value varies
depending on
the grid code.
The displayed
value prevails.
The default
s
value varies
depending on
the grid code.
The displayed
value prevails.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Value Range
Remarks
[100, 115]
This parameter
is displayed
when Voltage
rise
suppression is
set to Enable.
The value of
Voltage rise
suppression
active derating
[100, 115]
point must be
greater than
that of Voltage
rise
suppression
reactive
adjustment
point.
Disable
N/A
Enable
1100 V
N/A
SUN2000:
[0.1, 5]
Others: [0.1,
2.5]
[0.2, 20.0]
This parameter is
displayed if
Frequency
change rate
protection is set to
Enable.
This parameter is
[20, 800]
set to 360 by
default if the
Australian AS4777
grid code is
selected, and to
300 by default if
the Brazilian
ABNT NBR
16149 or South
African SA_RPPs
grid code is
selected.