2.3 Nameplate Description

A nameplate is attached at the back of the SmartLogger. The content of the nameplate
includes the SmartLogger model, rated power specifications, and certification marks.
2-5
Issue Draft A (2017-02-15)
Port (Silk
Screen)
AI1–AI7
PT1, PT2
AO1–AO4
DI1–DI8
If the APP fails to connect to the SmartLogger or you have forgotten the IP address, you
can press the Default key to reset the Bluetooth module or restore the IP address to the
default IP address (192.168.0.10).
To reset and restart the Bluetooth module, press and hold down the Default key for
3–10s until the BLU indicator blinks at short intervals (0.125s on and 0.125s off) and all
other indicators are off, and then release the Default key.
To restore the IP address to the default IP address, press and hold down the Default key
for more than 10s until the RUN indicator blinks at short intervals (0.125s on and
0.125s off) and all other indicators are off, and then release the Default key. The
operation is valid within 5 minutes.
shows the nameplate of the SmartLogger2000-10-C.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Function
Description
Analog input
AI1 supports 0–10 V voltage input
(passive); AI2–AI7 support 0–20 mA and
4–20 mA current input (passive).
Analog input
Analog output
4–20 mA and 0–20 mA current output.
Digital parameter
Connects to a dry contact input.
input
2 Product Overview
PT1 supports the connection to a
three-wire or two-wire PT100/PT1000
temperature sensor.
PT2 supports the connection to only a
two-wire PT100/PT1000 temperature
sensor.
Figure
10