SmartLogger2000-(10-C, 11-C)
User Manual
Protection Parameters
Table 7-3 Parameter description
No.
Parameter
1
Insulation
resistance
protection
Feature Parameters
Table 7-4 Parameter description
No.
Parameter
Description
1
MPPT
When the SUN2000 is
multi-peak
used in scenarios
scanning
where PV strings are
obviously shaded,
enable this function.
Then the SUN2000
will perform MPPT
scanning at regular
intervals to locate the
maximum power.
2
MPPT
Specifies the MPPT
multi-peak
multi-peak scanning
scanning
interval.
interval
Issue Draft A (2017-02-15)
Description
To ensure device safety,
the SUN2000 detects the
insulation resistance of the
input side to the ground
when it starts a self-check.
If the detected value is less
than the preset value, the
SUN2000 does not start.
Unit
N/A
min
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Default Value
The default value
for a 1000 V
SUN2000 is 0.1,
and the default
value for 1100 V
and 1500 V
SUN2000s is
0.05.
Default
Value Range
Value
Disable
Disable
Enable
15
[5, 30]
7 WebUI
Value Range
The value range for a
1000 V SUN2000 is
[0.033, 1], and the value
range for 1100 V and
1500 V SUN2000s is
[0.033, 1.5].
Remarks
The scanning
interval is set by
MPPT multi-peak
scanning interval.
This parameter is
displayed only when
MPPT multi-peak
scanning is set to
Enable.