SmartLogger2000-(10-C, 11-C)
User Manual
Power Meter Parameter and Grid Connection Feedback Parameter Configuration
To configure the power meter parameters and grid connection feedback parameters, see
7.9.2.3 Setting Power Meter
Active Power Control
Because of permission restriction, log in as Special User. Choose Settings > Active Power
Control to access the target page.
The remote scheduling command sent by the SmartLogger controls the active power output of
the PV plant in analog input mode. Set Active Power Control Mode to AI remote control.
Before setting Active Power Control Mode to AI remote control, ensure that connections
between the SmartLogger and the remote terminal control system are correct.
Figure 8-14 AI remote control
Issue Draft A (2017-02-15)
Value identification precision identifies the remote scheduling command variation threshold in the
case of active power adjustment to prevent frequent control command sending due to the sampling
deviation. Its setting range is 1% to 100%.
Power station total rated power (Pn) is the maximum on-grid power of the PV plant agreed by the
PV plant and the power grid company. Confirm this parameter value with the power grid company
and set it correctly.
If Reactive power control mode is set to Dry contact remote control, Active Power Control
cannot be set to AI remote control.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Parameters.