CP.30 Analog output 1 / function
CP.30 defines the function of analog output 1. The output at the analog output is always
made in a range of 0...+10 V. Negative values are inverted and the output is displayed in
a positive value.
Value Function
0
Absolute actual frequency CP.1
1
Absolute set frequency CP.2
2
Actual frequency CP.1
3
Set frequency CP. 2
4
Output voltage CP.9
5
DC link voltage CP.7
6
Apparent current CP.4
7
Active current ru.17
8...10 reserved
11
Absolute active current ru.17
12
Power stage temperature ru.38
13...21 reserved
22
Analog input before amplification (ru.27)
23
Analog input after amplification (ru.28)
24...25 reserved
26
Active power ru.81
CP.32 Transistor output / function (term. X2A.10)
The switching level of CP.32 is pre-set to 4,00. Value range see CP.33.
CP.33 Relay output 1 / function (terminals X2A.11...13)
The switching level of CP.33 is adjusted by CP.34.
Value Function
0
No function (generally off)
1
Generally on
2
Run signal; also by DC-braking
3
Ready signal (no error)
4
Fault relay
5
Fault relay (without auto-reset)
6
Warning or error message at abnormal stopping
7
Overload pre-warning (OL)
8
Overtemperature pre-warning (OH)
9
External overtemperature
10
Motor protection pre-warning (OH2)
11
Interior temperature pre-warning (OHI)
12
Cable breakage 4...20 mA on analog input 1
14
max. constant current (Stall, CP.25) exceeded
15
max. ramp current (LA-Stop, CP.24) exceeded
16
DC-braking active
20
Actual value = set value (CP.3 = Fcon; rcon; not at noP, LS, error, SSF)
21
Accelerate (CP.3=FAcc, rAcc, LAS)
22
Decelerate (CP.3 = FdEc, rdEc, LdS)
GB - 26
Scaling factor
0...100 % (0...±100 %)
0...100 Hz
0...100 Hz
0...±100 Hz
0...±100 Hz
0...500 V
0...1000 V
0...2 • rated current
0...2 • ±rated current
0...2 • rated current
0...100 °C
0...100 %
0...400 %
0...±2 • Rated power
further on next side