Activation Of The Temperature Input (Only Housing B) - KEB combivert B6 Installation Manual

Table of Contents

Advertisement

Annex A
400 V
Storage period > 3 years
Input voltages as before, however double the times per year. Eventually change
capacitors.
After expiration of this start-up the KEB COMBIVERT can be operated on nominal rating
conditions or delivered to a new storage.
A.5

Activation of the temperature input (only housing B)

The parameter Pn.12 determines the response of the drive when terminals T1, T2 of terminal
strip X1B (only housing B) are open. The function is switched off at factory setting (value
"7"), so the terminals must not be bridged. The following responses can be adjusted:
pn.12
Display
0
E.dOH
1*
A.dOH
2*
A.dOH
3
A.dOH
4*
A.dOH
5*
A.dOH
6*
7
*) If the motor is still too hot after 10 seconds, the error E.dOH is triggered and the modulation
is switched off ! If overheat no longer exists, the message E.ndOH (or A.ndOH) is output.
Only then the error can be reset or the automatic restart can be carried out.
It is neccessary to change into the application mode to activate the temperature input. There
the parameter Pn.12 can be set according to the table above. The following example shows
how to change the parameter Pn.12 to value "7".
Response
Immediate disabling of modulation
Quick stopping / disabling of modulation
after reaching speed 0
Quick stop / holding torque at speed 0
Immediate disabling of modulation
Quick stopping / disabling of modulation
after reaching speed 0
Quick stop / holding torque at speed 0
No effect to the drive. An output can be set
none
with CP.32/33 value „11".
No effect to the drive. Malfunction is not
none
present !
0...280 V
280...400 V
400...540 V
15 min
15 min
1 h
Restart
Remove fault; reset
Autoreset, if no fault is
present
inapplicable
GB - 37